Operating the contactor panel with panel width 600 mm
158
NXAIR /
≤ 40 kA
110-0134.9 / 14
Procedure
NOTICE
Maloperation
All interlocks are only released when the contactor truck is in a stable end
position.
Rack the contactor truck absolutely until end position.
To release the actuating opening for the double-bit key, lift the operating slide and hold it.
To release access to the contactor truck, insert the double-bit key and turn
counter-clockwise as far as it will go (that is
90°).
Fig. 277: Lifting operating slide and
turning the double-bit key
counter-clockwise
Fig. 278: Operating shaft for
racking crank
Push the racking crank for moving the contactor truck onto the operating shaft, and turn
counter-clockwise as far as it will go.
Remove the racking crank for moving the contactor truck.