Operating the contactor panel with panel width 435 mm
140
NXAIR /
≤ 40 kA
110-0134.9 / 14
Permissible HV HRC fuse-links
The specified SIBA HV HRC fuse-links are motor protection back-up fuse-links according to IEC 60282-1.
The dimensions of the HV HRC fuse-links correspond to DIN 43625.
NOTICE
Maloperation
Contactor trucks are exclusively designed for operation with specific HV HRC
fuse-links. Using other types of fuse-links may cause damages on the panel.
Use only the fuse-link types listed in the following table.
Do not mount bridging links instead of HV HRC fuse-links.
Selection table for HV HRC fuse-links
Rated
voltage
U
r
[kV]
Rated current
I
r
[A]
Dimension
“e” [mm]
Number of
fuse-links
permitted per
phase
Order details
(SIBA)
Order details
(Inter-teknik)
7.2
50
442
1
3010853.50
+S68T.12KV.442.050.08-7.2
63
1
3010853.63
+S68T.12KV.442.063.08-7.2
80
1
3010853.80
+S68T.12KV.442.080.08-7.2
100
1
3010853.100
+S4T.12KV.442.100.08-7.2
125
1
3010953.125
+S4T.12KV.442.125.08-7.2
160
1 or 2
3010953.160
+S4T.12KV.442.160.08-7.2
200
1 or 2
3011054.200
+S4T.12KV.442.200.08-7.2
250
1 or 2
3011054.250
+S4T.12KV.442.250.08-7.2
315
1
3011054.315
+S4T.12KV.442.315.08-7.2
Supplier information : www.siba-fuses.com
Supplier information : www.inter-teknik.com
Rated
voltage
U
r
[kV]
Rated current
I
r
[A]
Dimension
“e” [mm]
Number of
fuse-links
permitted per
phase
Order details
(SIBA)
Order details
(Inter-teknik)
12
50
442
1
3010153.50
+S68T.12KV.442.050.08
63
1
3010153.63
+S68T.12KV.442.063.08
80
1
3010253.80
+S68T.12KV.442.080.08
100
1
3010253.100
+S4T.12KV.442.100.08
125
1 or 2
3010253.125
+S4T.12KV.442.125.08
160
1 or 2
3010353.160
+S4T.12KV.442.160.08
Supplier information : www.siba-fuses.com