Operating the contactor panel with panel width 435 mm
122
NXAIR /
≤ 40 kA
110-0134.9 / 14
13.13 Operating conditions without auxiliary voltage
Contactor panels with electromagnetic interlock for racking the contactor truck (optional) plus mechanical
closing latching for the contactor (optional) are equipped with an additional feature.
In case the auxiliary voltage is disconnected, the electromagnetic interlock can be unlocked manually. This
manual unlocking is operated on the high-voltage door with a lever. This lever is padlocked during standard
operating conditions.
NOTICE
Maloperation
Without auxiliary voltage, turning the double-bit key is mechanically interlocked.
Do
not
try to turn the double-bit key while the mechanical interlock is
active.
Perform manual unlocking of the electromagnetic interlock to release
turning of the double-bit key.
In addition to these instructions, instruction labels on the high-voltage door
inform about the operation of the manual unlocking:
Fig. 201: Manual unlocking,
padlocked
Fig. 202: Instruction labels on high-voltage door
Racking the contactor truck to test position
INFORMATION
Unexpected switching noise and vibration
If the contactor is in CLOSED position before starting the procedure, turning the
double-
bit key 90° opens the contactor. This causes a short loud noise and low
vibration.
Expect switching noise and low vibration from inside the contactor when
turning the double-bit key.