Operating the removable voltage transformers
264
NXAIR /
≤ 40 kA
110-0134.9 / 14
Fig. 482: Pushing the contact cap into the housing
To lock the contact cap, insert both ends of the tool in the openings of the contact cap and
turn counter-clockwise as far as it will go.
Fig. 483: Locking the contact cap
Perform replacement with all other fuse-links.
✓
The protection fuse-links have been replaced.
INFORMATION
Final procedure steps
Next, insert the removable voltage transformers into the panel. After
closing the high-voltage door, the panel can be integrated into the course
of operation again.