Operating the circuit-breaker panel
110-0134.9 / 14
NXAIR /
≤ 40 kA
69
To close the actuating opening, push the operating slide down as far as it will go.
Fit a padlock (optional) to the operating slide and close it.
✓
The feeder is de-earthed.
10.18 Removing the low-voltage connector
Preconditions
•
Withdrawable circuit-breaker / circuit-breaker truck in test position
•
Spring energy store in the circuit-breaker discharged
•
Auxiliary voltage for the panel disconnected
•
High-voltage door open
•
Low-voltage connector plugged on
Procedure
To detach the low-voltage connector, push the longitudinal fastener (1) of the coupling
upwards.
Remove the low-voltage connector (2) carefully to the front.
Fig. 107: Removing the low-voltage connector
Hang the low-voltage connector into the support located underneath the low-voltage
compartment.
Fig. 108: Low-voltage connector stowed away