![Siemens NK8000 MP4.40 Series Application & Planning Download Page 74](http://html.mh-extra.com/html/siemens/nk8000-mp4-40-series/nk8000-mp4-40-series_application-and-planning_374611074.webp)
NK8000 application examples
74
Building Technologies
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
CPS Fire Safety
09.2016
Fig. 47 Local and network-wide interactions on NK823x
Note:
Network-wide interactions and dial-up connections are not currently compatible.
Limitations:
Local and network-wide interactions are limited to the following subsystems:
-
FS20/FS720
(NK823x only)
-
CS11 AlgoRex
-
FC700A
-
CS1115/FC330A
(NK823x only)
-
XLS
-
STT20, STT2410
-
SIGMASYS/ D100
-
SI410/420
-
CS6 Guarto
-
DF8000
-
NK8000 DF80xx digital I/O modules/systems
-
MK7022 Cerloop interface
-
Philips-Burle video switcher
Note:
NK8000 is not certified as part of an EN54-2 fire detection system. There-
fore, NK8000 interactions should only be used in applications where they are not
in conflict with EN54 standards or national guidelines or regulations (e.g. not for
common control of remote transmission devices).
The NK823x units are capable of
network-wide interactions
via BACnet/IP to sub-
systems connected to other NK823xs. Network-wide interactions on the NK823x via
BACnet/IP are possible for the same subsystems as local interactions.
®
For the list of supported 3
rd
party add-on subsystems, see section 3.4 p. 69.
Summary of Contents for NK8000 MP4.40 Series