![Siemens NK8000 MP4.40 Series Application & Planning Download Page 41](http://html.mh-extra.com/html/siemens/nk8000-mp4-40-series/nk8000-mp4-40-series_application-and-planning_374611041.webp)
Automation level configurations
41
Building Technologies
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
CPS Fire Safety
09.2016
Subsystems that can be connected in this way
Type
Name
Supported by
MM8000
MP4.81
MK8000
MP4.81
Fire panel
FS20 Sinteso
X
X
Fire panel
FS720
Cerberus PRO
X
X
Fire panel
STT20
X
X
Building
automation
DESIGO PX
X
Additional components required for the various management station types
Type
Additional
components
Name
Version
Foreign station
OPC client head end
Any OPC DA/UA
compliant client
OPC DA2.0x
OPC UA 1.02
OPC Server
MK8000
MP4.81
BACnet Driver
NS8011
MP4.81
MM8000
BACnet Driver
NS8011
MP4.81
Limits and restrictions
Type
Version
Restrictions
MM8000 MP4.81
Up to 64 BACnet devices (FCxx/FTxx and/or
DESIGO PX) per Server/FEP stations can be
connected.
‡
Note:
Panels from an FS20 system (or project)
cannot be split to communicate to 2 separate
FEPs (2 BACnet clients).
FS20 Sinteso/FS720 Cerberus PRO Systems:
–
Limit 16 FCxx/FTxx per SAFEDLINK loop
–
Limit 64 FCxx/FTxx on multiple SAFEDLINK
loops
–
Max. 2 GAP stations in FCnet/SAFEDLINK
topology
–
Max. 2 BACnet clients
STT20 in FCnet/SAFEDLINK:
–
1 FCnet/SAFEDLINK network with
- max. 10 STT20 (FCGW20-02) and
- max. 12 FC20xx panels
DESIGO PX displays events to indicate when
conditions are abnormal – no additional informa-
tion regarding an event such as causes or condi-
tions is available on the management station.
MK8000 MP4.81
DESIGO PX not supported.
‡
See
MM8000 MP4.81 Release Notes
(Doc. # A6V10062509) for PX models and quantity supported
Summary of Contents for NK8000 MP4.40 Series