Automation level configurations
35
Building Technologies
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
CPS Fire Safety
09.2016
Subsystems that can be connected in this way
Type
Name
Supported by
MM8000
MP4.81
MK8000
MP4.81
Intrusion panel
SI410/420
X
X
Network devices required (for LAN tunnelling)
Type
Name
Version
LAN/RS-232 adapter
(internal)
SMN36/42/43
See SI410/420 documentation
LAN/RS-232 adapter
(external)
See LANTRONIX documentation
Additional components required for the various management station types
Type
Additional
components
Name
Version
Foreign station
OPC client head end Any OPC DA/UA
compliant client
OPC DA2.0x
OPC UA 1.02
OPC Server
MK8000
MP4.81
SI410/420 driver
NS8014
LAN/RS-232
software
(for LAN tunnelling)
LANTRONIX
redirector
(or equivalent)
See
LANTRONIX
documentation
MM8000
SI410/420 driver
NS8014
MP4.81
LAN/RS-232
software
(for LAN tunnelling)
LANTRONIX
redirector
(or equivalent)
See
LANTRONIX
documentation
Limits and restrictions
Type
Version
Restrictions
MM8000 MP4.81
–
Connectivity limited to number of serial and
virtual serial ports.
–
Encryption option of the Ethernet modules not
supported.
–
GSM option on SMN43 not supported.
–
Up to 250 SI410/420 intrusion panels can be
connected per SI410/420 driver.
MK8000