Automation level configurations
50
Building Technologies
049_DMS_DMS8000_Application_Specification_Planning_MP4.81_A6V10063710_a_en.doc
CPS Fire Safety
09.2016
3.2.12 NK82xx LAN/WAN configuration
Fig. 32 NK8000 LAN/WAN configuration example
System architecture
This configuration allows for integration of a number of Cerloop (proprietary Class A
loop), Cerban and/or RS485 connectable control panels. In addition it allows for CS6
Guarto integration via LON-bus. The NK82xx Ethernet Ports provide the liaison to
MM8000/MK8000.
Additionally, the NK82xx provides serial connectivity to a local host
(MM8000/MK8000) using an RS-232 line via CMSDL protocol.
Communication/connection
The NK82xx is connected on the upstream side via Ethernet to the MM8000 and/or
the MK8000, and on the downstream side via serial lines and/or via LON-bus to a
number of different fire & security control units.
Dial-up lines can optionally be used as a backup connection in the event the network
is down, or as a primary connection when no network is present.
®
For supported downstream configurations/protocols of NK82xx please refer to the
NK82xx-Ethernet Port Datasheets.
To learn how to obtain these documents, see the
Documentation resource informa-
tion
section on page 5.