System Messages
C-9
MP270 Equipment Manual
Release 01/99
Remedy
Effect/Cause
Number
190006
The tag is not updated because it is not possible to
map the PLC type in the tag type.
Check the configuration.
190007
The tag values are not modified because the
connection to the PLC has been terminated or the tag
is offline.
Switch online or re-establish
connection to the PLC.
190008
The threshold values configured for the tag have been
violated, e.g. by
–
an entered value,
–
a function,
–
a script.
Observe the configured or current
threshold value of the tag.
190009
An attempt has been made to assign a value to a tag
which is outside the value range permitted for this
type.
E.g. a value of 260 entered for a byte
tag or a value of
-3 for a signless word tag
.
Observe the value range for the
tag type.
190010
The tag is described with values too often (e.g. in a
loop triggered by a script).
Values are lost because the maximum of 100 event
have been stored in the buffer.
Increase the time interval between
the multi-writing tasks.
190011
There are two causes for this message:
–
The value entered could not be written to the
configured PLC tag because it was either above
or below the value range.
The input is rejected and the original value is
reset.
–
Connection to the PLC has been interrupted.
Ensure that the value entered is
within the value range of the PLC
tags.
Check the connection to the PLC.
190012
It is not possible to convert a value from a source
format to a target format, e.g.:
–
A value should be assigned to a counter which is
outside the valid, PLC-dependent value range.
–
A tag of the type
Integer should be assigned a
value of the type
String.
Check the value range or type of
the variable.
190100
The area pointer is not updated because the
configured address for this area pointer is not
available.
Type:
1
Event messages
2
Alarm messages
3
PLC acknowledgment
4
Operating unit acknowledgment
5
LED assignment
6
Trend request
7
Trend transfer 1
8
Trend transfer 2
No.:
is the consecutive number displayed in ProTool/Pro.
Check the configuration.
Summary of Contents for Multi Panel MP270 SIMATIC HMI
Page 8: ...Preface vi MP270Equipment Manual Release01 99 ...
Page 18: ...Functionality 2 4 MP270EquipmentManual Release01 99 ...
Page 36: ...MP270 Operation 4 14 MP270Equipment Manual Release01 99 ...
Page 64: ...System Settings 6 8 MP270Equipment Manual Release01 99 ...
Page 82: ...Unit Description 8 8 MP270Equipment Manual Release01 99 ...
Page 90: ...Maintenance Upkeep 10 4 MP270Equipment Manual Release01 99 ...
Page 92: ...APPENDICES J 2 MP270Equipment Manual Release01 99 ...
Page 98: ...Technical Data A 6 MP270Equipment Manual Release01 99 ...
Page 114: ...System Messages C 14 MP270Equipment Manual Release01 99 ...
Page 144: ...Index Index 8 MP270Equipment Manual Release01 99 ...