System Messages
C-5
MP270 Equipment Manual
Release 01/99
Remedy
Effect/Cause
Number
80006
Since archiving is not possible, this causes a
permanent loss of the functionality.
In the case of databases, check
whether the corresponding data
source exists and start up the
system again.
80008
Since archiving is not possible, this causes a
permanent loss of the functionality.
Restart the system when the full
functionality is required.
80010
Since the path was incorrectly entered in ProTool, this
causes a permanent loss of the functionality.
Configure the path for the
respective archive again and
restart the system when the full
functionality is required.
80011
Target archives are open.
You have two minutes in which to
close the target archive, then a
new attempt is made.
80012
Archive values are stored in a buffer. If the values are
read to the buffer faster than they can be physically
written (e.g. using a hard disk), overloading may occur
and recording is then stopped.
Archive less values.
Or increase the recording interval.
80013
The overload status no longer applies. Archiving
resumes the recording of all values.
–
80014
The same action was triggered twice in quick
succession. Since the process is already in operation,
the action is only carried out once.
–
110000
The operating mode status has been changed. The
operating mode is now offline.
–
110001
The operating mode status has been changed. The
operating mode is now online.
–
110002
The operating mode status has not been changed.
Check the connection to the PLCs.
Check whether the address area
for the area pointer “Coordination”
in the PLC is available.
120000
The trend is not displayed because an incorrect axis
to the trend, or incorrect trend, has been configured.
Change the configuration.
120001
The trend is not displayed because an incorrect axis
to the trend, or incorrect trend, has been configured.
Change the configuration.
120002
The trend is not displayed because the tag assigned
tries to access an invalid PLC address.
Check whether the data area for
the tag exists in the PLC, the
configured address is correct or
the value range for the tag is
correct.
130000
The action was not executed.
Close other applications.
Delete files no longer required from
the hard disk.
130001
The action was not executed.
Delete files no longer required from
the hard disk.
130002
The action was not executed.
Close other applications.
Delete files no longer required from
the hard disk.
Summary of Contents for Multi Panel MP270 SIMATIC HMI
Page 8: ...Preface vi MP270Equipment Manual Release01 99 ...
Page 18: ...Functionality 2 4 MP270EquipmentManual Release01 99 ...
Page 36: ...MP270 Operation 4 14 MP270Equipment Manual Release01 99 ...
Page 64: ...System Settings 6 8 MP270Equipment Manual Release01 99 ...
Page 82: ...Unit Description 8 8 MP270Equipment Manual Release01 99 ...
Page 90: ...Maintenance Upkeep 10 4 MP270Equipment Manual Release01 99 ...
Page 92: ...APPENDICES J 2 MP270Equipment Manual Release01 99 ...
Page 98: ...Technical Data A 6 MP270Equipment Manual Release01 99 ...
Page 114: ...System Messages C 14 MP270Equipment Manual Release01 99 ...
Page 144: ...Index Index 8 MP270Equipment Manual Release01 99 ...