System Messages
C-4
MP270 Equipment Manual
Release 01/99
Remedy
Effect/Cause
Number
60011
An attempt was made to copy a file to itself.
It is possible that the Windows NT user has no access
rights to one of the two file.
Check the path of the
source
-
/target
file.
Using Windows NT with NTFS:
The user executing ProTool/Pro RT
must be granted access rights for
the files.
70010
The application could not be started because it could
not be found in the path specified or insufficient
memory space was available.
Check whether the application
exists in the specified path or close
other applications.
70011
The system time could not be modified This may be
due to the following:
–
an impermissible time was transferred in the PLC
job,
–
the Windows NT user has no user rights to modify
the system time.
Check the time which is to be set.
Under Windows NT: The user
executing ProTool/Pro RT must be
assigned the rights to modify the
system time from Windows NT
(administration/user manager,
guidelines).
70012
An error occurred when executing the function “Exit
Runtime” with the option “Exit also Windows”.
Windows and ProTool/Pro RT are not terminated.
A possible cause is that other applications cannot be
terminated.
Terminate all applications currently
running.
Then terminate Windows.
70013
The system time could not be modified because an
invalid value was entered. Incorrect separators may
have been used.
Check the time which is to be set.
70014
The system time could not be modified This may be
due to the following:
–
an impermissible time was transferred
–
the Windows NT user has no user rights to modify
the system time,
–
Windows rejects the setting request.
Check the time which is to be set.
Under Windows NT: The user
executing ProTool/Pro RT must be
assigned the rights to modify the
system time from Windows NT
(administration/user manager,
guidelines).
70015
The system time could not be read because Windows
rejects the reading function.
–
70016
An attempt was made to select a screen by means of
a function or job. This is not possible because the
screen number specified does not exist.
Or: a screen could not be generated due to
insufficient system memory.
Check the screen number in the
function or job with the screen
numbers configured.
Refer the number to a screen, if
necessary.
80001
–
Store the file or table by executing
a ‘move’ or ‘copy’ function.
80002
A line is missing in the specified archive.
–
80003
The copying process for archiving was not successful.
In this case, it is advisable to check any subsequent
system messages, too.
–
80005
The copying process for archiving was not successful.
If an automatic trigger is used for archiving, data may
have been lost.
–
Summary of Contents for Multi Panel MP270 SIMATIC HMI
Page 8: ...Preface vi MP270Equipment Manual Release01 99 ...
Page 18: ...Functionality 2 4 MP270EquipmentManual Release01 99 ...
Page 36: ...MP270 Operation 4 14 MP270Equipment Manual Release01 99 ...
Page 64: ...System Settings 6 8 MP270Equipment Manual Release01 99 ...
Page 82: ...Unit Description 8 8 MP270Equipment Manual Release01 99 ...
Page 90: ...Maintenance Upkeep 10 4 MP270Equipment Manual Release01 99 ...
Page 92: ...APPENDICES J 2 MP270Equipment Manual Release01 99 ...
Page 98: ...Technical Data A 6 MP270Equipment Manual Release01 99 ...
Page 114: ...System Messages C 14 MP270Equipment Manual Release01 99 ...
Page 144: ...Index Index 8 MP270Equipment Manual Release01 99 ...