5 System Parameters
International English
MICROMASTER 440 Operating instructions
52
6SE6400-5CA00-0BP0
5.1
Introduction to MICROMASTER System Parameters
The parameters can only be changed by using the Basic Operator Panel
(BOP), the Advance Operator Panel (AOP) or the Serial Interface.
Parameters can be changed and set using the BOP to adjust the desired
properties of the inverter, such as ramp times, minimum and maximum frequencies
etc. The parameter numbers selected and the setting of the parameter values are
indicated on the optional five-digit LCD display.
Read only parameters are indicated with r instead of P.
P0010 initiates “quick commissioning”.
The inverter will not run unless P0010 is set to 0 after it has been accessed.
This function is automatically perform if P3900 > 0.
P0004 acts as a filter, allowing access to parameters according to their
functionality.
If an attempt is made to change a parameter that cannot be changed in this
status, for example, cannot be changed whilst running or can only be changed
in quick commissioning, then
will be displayed.
Busy Message
In some cases - when changing parameter values - the display on the BOP
shows
for maximum of five seconds. This means the inverter is busy with
tasks of higher priority.
5.1.1 Access
Levels
There are three access levels available to the user; Standard, Extended and
Expert. The level of access is set by parameter P0003. For most applications, the
Standard and Extended levels are sufficient.
The number of parameters that appear within each functional group depends on
the access level set in parameter P0003. For further details regarding parameters,
see the Parameter List on the Documentation CD-ROM.