3 Commissioning
MICROMASTER 440 Operating instructions
6SE6400-5CA00-0BP0
37
3.2.4
Commission Overview with BOP or AOP
Prerequisites:
Mechanical and electrical Installation are completed.
Note
We recommend the commissioning according this scheme. Nevertheless an expert
user is allowed to do the commissioning without the filter functions of P0004.
3.2.4.1
Quick commissioning (P0010=1)
It is
important
that parameter P0010 is used for commissioning and P0003 is used
to select the number of parameters to be accessed. This parameter allows a group
of parameters to be selected that will enable quick commissioning. Parameters
such as Motor settings and Ramp settings are included.
At the end of the quick commissioning sequence, P3900 should be selected,
which, when set to 1, will carry out the necessary motor calculations and clear all
other parameters (not included in P0010=1) to the default settings. This will only
happen in the Quick Commissioning mode.
Setting the motor frequency
DIP Switch 2: Off = 50 Hz / ON = 60 Hz
Quick Commissioning P0010 = 1
See Section 3.2.4.1
Further Commissioning via P0004 and P0003
An overview of the parameter structure is given in
Section 5.3
For a detailed description of the parameter, see the
Parameter List.
Power ON