LMV Series
Technical Instructions
LV3-1000
Gas
Oil
Gas
Oil
U/S/O
Default
Range
Description
Parameter #
Fuel 0
Fuel 1
LEGEND -
Password Access: U = User, S = Service, O = OEM, U/S = View - User, Write - Service, S/O = View - Service, Write - OEM
Shaded Parameters = Frequently Used. ** Parameters = Must Set. Fuel 1 parameters for LMV36 only.
Parameter Name
601:00 = 1
601:01 = 0
0-1
1
0-1
602:00 = 0
602:01 = 0
0-1
0
0-1
606:00 = 1.7°
606:01 = 1.7°
0.5-4.0°
1.7°
0.0-4.0°
611:00 = 0
611:01 = 0
0-3
0
0-3
609
Reference Point**
-
612
Determines the type of reference of the actuators. These settings should be left at the default values of 0.
Index 00 = fuel actuator. Index 01 = air actuator
0 = standard
1 = range stop in the usable range
2 = internal range stop (SQN1… actuators only)
3 = both
Note:
The type of reference of the air actuator can only be set under parameter 611 and is not displayed
under parameter 612.
Position Tolerance
Reference Type
Determines the direction of rotation of the SQM33 actuators. The descriptions of the rotation are valid
when the actuator shaft is pointed at your eye.
Index 00 = fuel actuator.
Index 01 = air actuator
0 = counterclockwise
1 = clockwise
Note:
The direction of rotation of the air actuator can only be set under parameter 602 and is not
displayed under parameter 609.
Rotation Direction**
600 Level: Actuator and VSD Configuration
Determines the reference point of the SQM33 actuators. The actuators will reference after a normal
shutdown, lockout, or loss of power to the LMV3. In order to reference, the actuators must drive outside of
their 0-90° operating range. This parameter sets whether the actuators will reference closed (<0°) or open
(>90°).
Index 00 = fuel actuator.
Index 01 = air actuator
0 = closed (<0°)
1 = open (>90°)
Note:
The reference point of the air actuator can only be set under parameter 601 and is not displayed
under parameter 608.
-
601
-
602
-
606
-
611
-
Determines the allowed tolerance on the position of the actuators. If the actuator's position differs by
greater than this amount from the expected position, a lockout occurs. The default setting of 1.7° is
recommended.
Index 00 = fuel actuator. Index 01 = air actuator
Note:
The allowed tolerance of the air actuator can only be set under parameter 606 and is not displayed
under parameter 610.
-
S/O
-
610
608
SCC Inc.
Page 13
Section 3
Summary of Contents for LMV3 series
Page 1: ...Combustion Controls LMV3 Linkageless Burner Management System www scccombustion com ...
Page 2: ...Intentionally Left Blank ...
Page 41: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 13 Section 2 ...
Page 42: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 14 SCC Inc ...
Page 43: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 15 Section 2 ...
Page 44: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 16 SCC Inc ...
Page 45: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 17 Section 2 ...
Page 46: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 18 SCC Inc ...
Page 223: ...Intentionally Left Blank ...