LMV Series
Technical Instructions
LV3-1000
Gas
Oil
Gas
Oil
U/S/O
Default
Range
Description
Parameter #
Fuel 0
Fuel 1
LEGEND -
Password Access: U = User, S = Service, O = OEM, U/S = View - User, Write - Service, S/O = View - Service, Write - OEM
Shaded Parameters = Frequently Used. ** Parameters = Must Set. Fuel 1 parameters for LMV36 only.
Parameter Name
244
-
344
-
VP Fill Time
3 sec
0.2-10 sec
If valve proving is performed, this specifies the length of time that the upstream valve (V1) is energized
(output X8-02.1). This will fill the volume between the main gas valves to line pressure. Sets the length of
phase 82.
Note:
The time it takes for the gas valve to be at least half open must be less than the maximum value for
this parameter.
245
-
345
-
VP Downstream Test
10 sec
0.2-60 sec
If valve proving is performed, this specifies the length of time that both the upstream and downstream
valves are closed. If the pressure between the valves falls during this period (enough to close the NC valve
proving pressure switch), then the downstream valve is leaking and the LMV3 will lockout. A longer time
period will produce a more sensitive test. Sets the length of phase 83.
246
-
346
-
LGPS Wait Time
10 sec
0.2-60 sec
If there is a lack of gas pressure (low gas pressure switch is open), then the LMV3 will wait this period of
time before attempting to relight, provided that parameter 223 (fuel 0) or 323 (fuel 1) is set to a number
larger than 1 (not typically done in North America). This time period will double on each successive
attempt to relight.
-
281
-
381
Oil Ignition Start
0
0-1
On oil trains, this setting defines the point at which the ignition transformer is energized during the startup
sequence:
0 = phase 38 (short pre-ignition, use parameter 266 or 366 to set the length of time)
1 = phase 22 (long pre-ignition)
248
284
348
384
Postpurge Time 3
1 sec
1-6480 sec
This setting defines the optional postpurge time. If a call for heat exists during this time, the LMV3 stops
postpurging immediately and goes directly to standby. Once the air pressure switch is proven open and the
actuators reach their home positions, the burner will startup provided a call for heat still exists. See
parameter 234/274/334/374 for information on the mandatory postpurge time. Sets the maximum length
of phase 78.
-
285
-
385
Pilot LGPS
0
0-1
Parameter only exists on an LMV36: On oil trains with a gas pilot, this setting defines whether or not a low
gas pressure switch is connected to input X5-01.2. If set to 0, input X5-01.2 is ignored on oil. If set to 1,
input X5-01.2 must be energized by the end of phase 38.
0 = low gas pressure switch not connected
1 = low gas pressure switch connected
-
286
-
-
Start Release HO
1
0-1
Parameter only exists on an LMV37: When running heavy oil, this setting defines the point in the startup
sequence when the start release for heavy oil (input X9-04.2) must be energized.
0 = only in phase 38
1 = phase 38-62
-
287
-
-
Max Time SRHO
45 sec
1-45 sec
Parameter only exists on an LMV37: When running heavy oil, this sets the maximum time to satisfy the
heavy oil start release in phase 38. The heavy oil start release is wired to input X9-04.2. After this period of
time, the LMV3 will either lockout or attempt to light-off again depending on the setting of parameter 195.
S
O
SCC Inc.
Page 10
Section 3
Summary of Contents for LMV3 series
Page 1: ...Combustion Controls LMV3 Linkageless Burner Management System www scccombustion com ...
Page 2: ...Intentionally Left Blank ...
Page 41: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 13 Section 2 ...
Page 42: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 14 SCC Inc ...
Page 43: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 15 Section 2 ...
Page 44: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 16 SCC Inc ...
Page 45: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 17 Section 2 ...
Page 46: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 18 SCC Inc ...
Page 223: ...Intentionally Left Blank ...