LMV Series
Technical Instructions
Document No. LV3-1000
SCC Inc.
Page 5
Appendix A
Fresh Air Damper (continued)
Operation
1.
When there is no call for heat from the RWF5x load controller, the internal contact
between terminals 1N and 1P will be open. Both CR-1 and CR-2 coils will be de-
energized, and the fresh air damper will be closed.
2.
When the RWF5x load controller receives a call for heat, the internal contact between
terminals 1N and 1P will close. Terminal 1P will be energized as long as the burner on /
off switch is on. Coil CR-1 will be energized, closing the CR-1 contact. As long as the
LMV3 is not in alarm (CR-3 contact is closed), the fresh air damper will begin driving
open.
3.
Once the fresh air damper drives fully open, the fresh air damper end switch will close,
and the burner will turn on.
4.
The fresh air damper will remain open until the fan turns off. Once the fan turns off,
contact CR-2 will open and un-latch the circuit.
Important Notes
1.
The described procedure cannot be used with continuous fan.
2.
The burner startup cycle will be lengthened by the stroke time of the fresh air damper
actuator.
Summary of Contents for LMV3 series
Page 1: ...Combustion Controls LMV3 Linkageless Burner Management System www scccombustion com ...
Page 2: ...Intentionally Left Blank ...
Page 41: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 13 Section 2 ...
Page 42: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 14 SCC Inc ...
Page 43: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 15 Section 2 ...
Page 44: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 16 SCC Inc ...
Page 45: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 17 Section 2 ...
Page 46: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 18 SCC Inc ...
Page 223: ...Intentionally Left Blank ...