Error
Code
Diag.
Code
Meaning for the LMV3 System
Corrective Action
Note:
Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes.
Any #
Control range limitation of VSD
A VSD speed error occurred. See diagnostics codes for more information.
1
Control range limitation at the bottom
This indicates that the LMV3 has decreased its signal to the VSD as much as
possible and the motor RPM is still too high.
1) Increase VSD / LMV3 ramp times.
2) Increase VSD braking if possible.
3) Ensure that the VSD and LMV3 are configured for the same analog
signal (0-10 VDC).
4) Re-standardize the speed. Be sure to check combustion after the re-
standardization.
2
Control range limitation at the top
This indicates that the LMV3 has increased its signal to the VSD as much as
possible and the motor RPM is still too low.
1) Increase VSD / LMV3 ramp times.
2) Check for filters, damping, or delays on the input signal to the VSD. The
VSD should respond to the input signal in a linear fashion.
3) Check speed sensor on motor for correct installation, especially the gap
between the sensor and the speed wheel.
4) Ensure that the VSD and LMV3 are configured for the same analog
signal (0-10 VDC).
5) Re-standardize the speed. Be sure to check combustion after the re-
standardization.
81
1
Interrupt limitation speed input
The LMV3 has detected an interruption on the speed input. Decrease the
electrical noise on the speed sensor wires. If the fault occurs continuously,
replace the LMV3.
Any #
Error during VSD's speed standardization
An error occurred while attempting to standardize the speed of the VSD.
See diagnostic codes for more information.
1
Timeout of standardization (VSD ramp down time too long)
Standardization timed out because the VSD took too long to ramp down at
the end of the standardization. Either decrease the ramp down time in the
VSD or increase the setting of parameter 523.
2
Storage of standardized speed not successful
Press the info button with any other button to cause a manual lockout,
then reset the fault and attempt to standardize again.
80
82
Section 6
Page 10
SCC Inc.
Summary of Contents for LMV3 series
Page 1: ...Combustion Controls LMV3 Linkageless Burner Management System www scccombustion com ...
Page 2: ...Intentionally Left Blank ...
Page 41: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 13 Section 2 ...
Page 42: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 14 SCC Inc ...
Page 43: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 15 Section 2 ...
Page 44: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 16 SCC Inc ...
Page 45: ...LMV Series Technical Instructions Document No LV3 1000 SCC Inc Page 17 Section 2 ...
Page 46: ...Technical Instructions LMV Series Document No LV3 1000 Section 2 Page 18 SCC Inc ...
Page 223: ...Intentionally Left Blank ...