FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
| CHAPTER 1
The ZIC-8B supports synchronized and non-synchronized strobes. This selection is
available in the Zeus tool under the detail properties for each ZIC-8B circuit. Audible
synchronization across multiple ZIC-8B cards is automatic as a part of the FireFinder-XLS
operating characteristics and strobe synchronization is done on a card basis (strobe
circuits within a ZIC card). Refer to document P/N 315-096363 for a list of strobes that
support synchronization.
ZIC-2C Zone Indicating Card The Model ZIC-2C adds support for 2 channel audio to the
ZIC-8B. The ZIC-2C replaces the signal routing board that is
installed on the ZIC-8B in the factory. It mounts in the same
location as the signal routing card and utilizes the same
mounting hardware. Three 8 pin headers and one 20 pin
header are also reused with the ZIC-2C.
RPM Printer Interface
The RPM Printer Interface provides a parallel port to the
FireFinder-XLS system. The RPM is compatible with the
PAL-1 printer.
TSP-40A
The TSP-40A Logging Printer provides a paper record of the
activity of the system. You may install one printer for each PMI/
PMI-2/PMI-3 interface on your FireFinder-XLS System. In
addition to the TSP-40A module, the TSP-XB U-Shaped Bracket
and Front Plate (P/N 500-849949) and TSP-XC Cable Kit (P/N
500-849950) must be ordered and installed.
CAB Enclosures
The FireFinder-XLS system can be housed in one of three
enclosures: CAB1, CAB2, or CAB3. The CAB1 is a single-
row enclosure that consists of a backbox, front door and
inner door that is shipped assembled. The CAB2 and
CAB3 are two-row and three-row enclosures respectively
with the backbox and doors (inner and outer) shipped
separately.
HTSW-1 Tamper Switch
The HTSW-1 Tamper Switch is a three-position switch that monitors
the opening of the FireFinder-XLS enclosure and reports a security
condition. Closing the door automatically returns the switch to its
normal operating position. The switch can be pulled out to indicate a
closed position for maintenance purposes.
Batteries
The BP-61 is a 24V 15 AH battery. The BP-61 is recommended
for the NFPA 72 Local and 72 Proprietary and the UL 1076
Systems. Battery size selection depends on System configura-
tion. See the Battery Calculation section of the PSC-12 Installa-
tion Instructions, P/N 315-033060, for further information.