3-8
OPERATION
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
| CHAPTER 3
Pressing the Details soft key takes
you to the Details screen as shown
in Figure 3-8. The Details screen
contains information that has been
entered using the Zeus program-
ming tool, such as additional
information about the alarm loca-
tion, the number of devices in alarm
(this number can be more than one
when the device is part of a
group), the alarm types, the name
and phone number of a contact
person, icons showing the fire
equipment in the area and icons
showing special conditions.
Press the Map soft key to display a
map showing the location of the
event, provided the information has
been programmed using the Zeus
tool. Refer to Figure 3-9. Maps can
be programmed to provide icons
showing the event type. These icons
are the same ones that represent
Alarm, Security, Supervisory and
Trouble on the PMI panel. The map
can also be programmed to show
the location of the PMI/PMI-2/PMI-3
(“You are here”). All members of a
group will display the same map.
List of Icons:
Trouble
(Fire or MNS)
MNS event
(priority 1 and 2)
Emergency (ULC)
Gas (UL)
Other (ULC)
Fire Alarm
Supervisory
Security (PMI/PMI-2 only)
When a security is detected, the yellow Security LED blinks, the System’s internal
audible pulses, and the event(s) display on the screen with a blinking exclamation
mark (!). This event listing displays the Event Custom Message, the Time of the event
occurrence and the Security Event Category (i.e., Door, Monitor Point, etc.).
In addition, the System responds to securities with other output functions (as
programmed in the Zeus tool).
An Acknowledge Security soft key displays in the bottom left corner of the screen.
Press this key to acknowledge each security and to silence the local audible. The
blinking exclamation point (!) then changes to a check mark (
9
). See Figure 3-6.
Contact: John Sample
Phone #: 973.555.1234
AREA FIRE EQUIP:
AREA CONTAINS:
DETAILS
MAP
DEVICES
BACK
ALARM LOCATION:
1st Floor Reception Area
- Lobby entrance
# Devices in ALARM: 3
ALARM TYPES:
Smoke, Heat, Flow
First Floor Reception Area
Figure 3-8
Alarm Details Screen
DETAILS
SHOP
LAV
HALL
RECEPTION
MAIN
STREET
SHIPPING
L
O
ADING
DOCK
MAP
DEVICES
BACK
First Floor Reception Area
Figure 3-9
Sample Map Screen