GCNET and Galactic Voice
6-11
CHAPTER 6
|
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Galactic Clear Manual
Galactic Clear Manual allows the user to cancel all manually activated functions in all
Buildings with a single switch press.
To clear all manually activated functions, follow the steps listed below:
1.
Depress the Galactic Clear Manual switch.
2.
All Emergency Page, Evacuation, and Alert activations will be canceled.
3.
All activated LEDs turn off.
FCC Trouble Sounder Switch When a trouble exists on the FCC or with any FCC hardware, the FCC Trouble
Sounder will be flashing yellow, and an audible will beep for one second every nine
seconds. Pressing the button will silence the audible for 24 hours. When silenced,
the LED will change to a solid yellow.
VIRTUAL LOGIC
GCNET provides virtual, supervised Inter-Building programmable logic via the virtual
VLIS and VLOS submodules. A logic output in one Building may be associated with
one or more logic inputs in one or more Buildings. The logic inputs provide both
Active criteria (indicating that the logic output in the other Building is active) and
Trouble criteria (indicating failure of the Inter-Building logic link).
VLIS
Virtual Logic Input Submodule has 16 inputs which can be programmed for inter-
building logic when combined with VLOS output devices.
VLOS
Virtual Logic Output Submodule has 16 relays which can be programmed for inter-
building logic when combined with VLIS input devices.