CAUTION
ALL WIRING MUST BE DONE AS DESCRIBED BELOW
TO OBTAIN SAFE AND PROPER SYSTEM OPERATION.
1.
Earth ground the FireFinder-XLS enclosure properly; see the latest edition of the
National Electrical Code or CAN/ULC-S524-01 Canadian Electrical Code for
approved methods. Conduit ground is NOT adequate.
2.
To wire the System in compliance with NEC Article 760, refer to the Power
Limited Wiring Instructions for the CAB1 Enclosure, P/N 315-033007, or the
CAB2-BB/CAB3-BB, P/N 315-033009, as applicable.
3.
INSULATE ALL CABLE DRAIN WIRES from any conduit or earth grounded
electrical box, including those in the FireFinder-XLS enclosure.
4.
Connect shield cable drain wire ONLY inside the FireFinder-XLS enclosure.
5.
For wiring outside the building, refer to the FireFinder-XLS Wiring Compatibility
Guide, P/N 315-034786.
For additional wiring
information, refer to this
manual or call Siemens
Industry, Inc. Technical
Support Department at
1-800-248-7976.
Copyright © 2001 - 2016, Siemens Industry, Inc.