6BMaintenance / Repair
53BTesting detectors
7
115 | 138
Building Technologies
007004_t_en_--
Fire Safety
2015-11-04
7.2.1
'Technical Ambient Supervision Message' performance
check
You cannot test whether the 'Technical Ambient Supervision Message' is
functioning correctly with test devices.
Checking can only take place indirectly:
You must know the current ambient temperature.
Enter the following parameters in the 'SintesoWorks' software:
–
A hysteresis range of 5 °C.
–
A temperature threshold which is at least 10 °C below the current ambient
temperature.
–
Alarming when value falls below threshold
The detector sends a signal to the control panel.
The 'Technical Ambient Supervision Message' is working correctly if the control
panel displays an alarm.
7.3
Testing detectors
Depending on the detector, testing may be performed with one or more of the
following accessories:
●
Detector exchanger and tester FDUD292
●
Intelligent detector tester FDUD293 (recommended)
●
Detector tester RE6
●
Test gas
–
REF8-S (recommended)
–
REF8
●
Hot air
–
RE7T Solo461 heat detector tester kit
The table below lists appropriate tools:
Detector
Detector
exchanger and
tester
Intelligent detector
tester
Test gas
Hot air
FDOOT241-x/-Ax (sensor mode 0)
X
X
X
X
FDOOT241-x/-Ax (sensor mode 1)
X
X
–
X
FDOOT241-x/-Ax (sensor mode 2)
X
X
X
–
FDOOT221
X
X
X
X
FDO2x1
X
X
X
–
FDT2x1
X
X
–
X
X
Suitable
-
Not suitable
Please observe the following information when testing: