Periphery board (250p) FCI2016
Description
1
5 | 46
Building Technologies
A6V10315038_f_en_--
Siemens Industry, Inc.
2016-02-25
1 Periphery board (250p) FCI2016
1.1 Description
The periphery board (250p) FCI2016 is used for fire control panels and voice alarm fire
control panels with max. 252 device addresses. The purpose of the periphery board is
to provide means for supervising and controlling various peripheral devices, such as
detectors and notification devices, and providing power for the entire panel. There is a
detector core on the periphery board, that is isolated from the rest of the periphery
board. An auxiliary output circuit (1.5 A, 24 V) provides power to remote devices or
internal modules. The integrated NAC circuit (NAC 1) provides up to 3 A of power for
max. 1 class A circuit or 3 A for each of max. 2 class B circuits. The periphery board
has expansion capabilities for leased line / city tie operation, a releasing circuit with 2
zones, and an additional NAC circuit (NAC 2).
The periphery board has a battery charger and battery switchover circuit for AC fail or
brownout. The battery charger is capable of charging up to 100 Ah batteries.