2.4 Configuration input power and battery
The periphery board has jumpers that are used to configure the system functions. The
jumper settings are described in the following sections.
2.4.1 Wiring power supply input and battery
Power supply 1 connection (170 W or 300 W)
Connection X301 must be used for a single power supply.
Jumper X305 must be plugged onto position 1-2.
Connection for power supply 2 (only 300 W)
Only one power supply (300 W) may be connected to X302.
A 2nd power supply (300 W) is only allowed in an housing (3HU).
Jumper X305 must be plugged onto position 2-3.
Battery connection
X301
1
GND
+
+26V
PSSI
2
3
4
BROO
X302
1
GND
+
+26V
PSSI
2
3
4
BROO
X303
BAT+
-
+
BAT-
1
2