2 Periphery board (500p) FCI2017
2.1 Description
The FCI2017 periphery board (500p) is used for fire control panels and voice alarm fire
control panels with max. 504 device addresses. The purpose of the periphery board is
to provide means for supervising and controlling various peripheral devices, such as
detectors and notification devices, and providing power for the entire panel. There are
2 detector cores on the periphery board, each isolated from the rest of the periphery
board, and each other. An auxiliary output circuit (1.5 A, 24 V) provides power to
remote devices or internal modules. The integrated NAC circuit (NAC 1) provides up to
3 A of power for max. 1 class A circuit or 3 A for each of max. 2 class B circuits. The
periphery board has expansion capabilities for leased line / city tie operation, a
releasing circuit with 2 zones, and an additional NAC circuit (NAC 2).
The periphery board has a battery charger and battery switchover circuit for AC fail or
brownout. The battery charger is capable of charging up to 100 Ah batteries.