Error_
Code_
1
Error_
Code_
2
Cause
Remedy
0xE1
0x01
Reserved bit set
Check and correct the parameters
0xE1
0x02
Invalid diagnostics enable bit set for operating mode
0xE1
0x03
Invalid hardware interrupt enable bit set for operating
mode
0xE1
0x07
Invalid coding for input delay
0xE1
0x0B
Invalid coding for pulse stretching
0xE1
0x0E
Invalid redundancy parameter assignment
A.2
Parameter assignment and structure of the module/channel
parameters
Structure of data record 128
Data record 128 has a length of 76 bytes.
It contains module parameters as well as channel or technology parameters of the 16 channels;