Article number
6DL1131-6BH00-0PH1
Interrupts/diagnostics/status information
Diagnostics function
Yes
Diagnoses
• Diagnostic information readable
Yes
• Monitoring the supply voltage
Yes; Module-wise
– parameterizable
Yes
• Monitoring of encoder power supply
Yes
• Short-circuit to M
Yes; Encoder supply to M, channel by channel
Diagnostics indication LED
• MAINT LED
Yes; Yellow LED
• Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
• Channel status display
Yes; green LED
• for channel diagnostics
Yes; red LED
• for module diagnostics
Yes; green/red LED
Potential separation
Potential separation channels
• between the channels
No
• between the channels and backplane bus
Yes
• between the channels and the power supply
of the electronics
No
Isolation
Isolation tested with
1 500 V DC/1 min, type test
Ambient conditions
Ambient temperature during operation
• horizontal installation, min.
-40 °C
• horizontal installation, max.
70 °C
• vertical installation, min.
-40 °C
• vertical installation, max.
60 °C
Dimensions
Height
115 mm
Depth
138 mm
Weights
Weight, approx.
135 g
Technical specifications
DI 16x24VDC HA
Equipment Manual, 10/2020, A5E39265608-AD
31
Summary of Contents for DI 16x24VDC HF
Page 6: ...Security information DI 16x24VDC HA 6 Equipment Manual 10 2020 A5E39265608 AD ...
Page 8: ...Preface DI 16x24VDC HA 8 Equipment Manual 10 2020 A5E39265608 AD ...
Page 10: ...2D Matrix code QR code EAN code DI 16x24VDC HA 10 Equipment Manual 10 2020 A5E39265608 AD ...
Page 36: ...Technical specifications DI 16x24VDC HA 36 Equipment Manual 10 2020 A5E39265608 AD ...