Parameter
Value range
Default
Parameter re‐
assignment in
RUN
Efficiency range
2
• None
• 0.05 s
• 0.1 s
• 0.2 s
• 0.5 s
• 1 s
• 2 s
None
Yes
Channel
Hardware interrupts positive
edge (Page 23)
2
• Enabled
• Disabled
Disabled
Yes
Channel
Hardware interrupts nega‐
tive edge (Page 24)
2
• Enabled
• Disabled
Disabled
Yes
Channel
Potential group (Page 24)
• Potential group of the left mod‐
ule (dark gray terminal block)
• New potential group (light gray
terminal block)
• No potential group (black termi‐
nal block)
Use potential
group of the left
module
No
Module
1
The wire break diagnostics can only be enabled when the "Check for wire break" parameter is enabled. If you use a simple
encoder contact, you need to connect a parallel resistor to enable wire break diagnostics in the open state (sensor resistance
for wire break diagnostics: 15 kΩ to 18 kΩ).
2
The input delay is switched off on all channels when high precision time stamping is activated. When high precision time
stamping is activated, pulse stretching and the rising/falling edge hardware interrupt are deactivated on all channels (not
adjustable).
6.2
Parameter reassignment
Definition
Each configuration change resets the corresponding reaction. Changing the configuration of a
function does not affect other functions.
6.3
Explanation of the module/channel parameters
6.3.1
Diagnostics, Missing supply voltage L+
Definition
Enabling of the diagnostics for missing or insufficient supply voltage L+.
Parameters
6.3 Explanation of the module/channel parameters
DI 16x24VDC HA
20
Equipment Manual, 10/2020, A5E39265608-AD
Summary of Contents for DI 16x24VDC HF
Page 6: ...Security information DI 16x24VDC HA 6 Equipment Manual 10 2020 A5E39265608 AD ...
Page 8: ...Preface DI 16x24VDC HA 8 Equipment Manual 10 2020 A5E39265608 AD ...
Page 10: ...2D Matrix code QR code EAN code DI 16x24VDC HA 10 Equipment Manual 10 2020 A5E39265608 AD ...
Page 36: ...Technical specifications DI 16x24VDC HA 36 Equipment Manual 10 2020 A5E39265608 AD ...