Configuration
4.10 Messages: E-mails (CP 1543SP-1)
CP 154xSP-1
78
Operating Instructions, 12/2019, C79000-G8976-C426-05
●
Enable identifier for processing status
If the option is enabled, every attempt to send returns a status with information about the
processing status of the sent message.
The status is written to the "PLC tag for processing status" (DWORD). If there are
problems delivering messages, you can determine the status via the Web server of the
CPU by displaying the value of the PLC tag there.
For information on the significance of the individual statuses, see section Processing
status of e-mails (CP 1543SP-1) (Page 95).
●
Include value
If you enable the option, the CP sends a value for the placeholder $$ from the memory
area of the CPU in the message.
Select a PLC tag whose value is integrated in the message. $$ can be the placeholder for
a variable with a simple data type up to a size of 32 bits.
The respective current value is entered in the message text instead of the placeholder $$.
To do this enter "$$" as a placeholder for the value to be sent in the message text.
Editor view: Arranging columns and rows
As with many other programs, you can also arrange the columns and sort the table
according to your needs in the message editor:
●
Arranging columns
If you click on a column header with the left mouse button pressed, you can move the
column.
●
Sorting objects
If you click briefly with the left mouse button on a column header, you can sort the objects
of the table in ascending or descending order according to the entries in this column. The
sorting is indicated by an arrow in the column header.
After sorting in descending order of a column the sorting can be turned off by clicking on
the column header again.