Program blocks
5.4 IF_CONF: SDT for the configuration data of the CP
CP 1243-7 LTE
116
Operating Instructions, 04/2017, C79000-G8976-C381-03
"Authorized phone number"
In STEP 7, the corresponding data is located in the "Security" parameter area.
Table 5- 8
IF_CONF_WakeupList
Parameter
Data type
Initial value
Description
Id
UINT
13
ID of the parameter field
Length
UINT
Length of the parameter field in bytes: 246
Mode
UINT
Validity (1, 2) - see above (general parameters)
WakeupPhone [1...10] ARRAY [1...10]
of STRING [22]
Phone number subscriber authorized to wake up
The asterisk (*) at the end of a call number is used a
placeholder for direct dialing numbers.
"Preferred mobile wireless networks"
In STEP 7, the corresponding data is located in the "Mobile wireless communications
settings" parameter area.
Table 5- 9
IF_CONF_PrefProvider
Parameter
Data type
Initial value
Description
Id
UINT
14
ID of the parameter field
Length
UINT
Length of the parameter field in bytes: 46
Mode
UINT
Validity (1, 2) - see above (general parameters)
Provider [1...5]
ARRAY [1...5]
of STRING [6]
Alternative mobile wireless networks with priority 1 to 5
into which the CP dials. Up to 5 networks can be config-
ured. No. 1 with highest priority, no. 5 with lowest priority.
Entry of the Public Land Mobile Network (PLMN) of the
network provider consisting of Mobile Country Code
(MCC) and Mobile Network Code (MNC).
Example (test network of Siemens AG): 26276
TeleService access (DNS name / IP address of the server)
Access data of the TeleService server (switching station).
In STEP 7, the corresponding data is located in the "Mobile wireless communications
settings" parameter area.
With IF_CONF_TS_Name only a TeleService server configured in STEP 7 can be changed
but no new one created. If you attempt to create the configuration of a TeleService server
with the block. the internal error 80E0 is output at TC_CONFIG.
Table 5- 10 IF_CONF_TS_Name
Parameter
Data type
Initial value
Description
Id
UINT
20
ID of the parameter field
Length
UINT
Length of the parameter field in bytes: 266
Mode
UINT
Validity (1, 2) - see above (general parameters)
ts_name
String [254]
Name of the TeleService server that can be resolved by
DNS or IP address as string