Program blocks
5.4 IF_CONF: SDT for the configuration data of the CP
CP 1243-7 LTE
Operating Instructions, 04/2017, C79000-G8976-C381-03
115
"Telecontrol server"
In STEP 7, the corresponding data is located in the "Partner stations" parameter area.".
This field is only used when the telecontrol server is addressed with a name that can be
resolved by DNS or when the IP address is to stored as a string.
Table 5- 5
IF_CONF_TCS_Name
Parameter
Data type
Initial value
Description
Id
UINT
6
ID of the parameter field
Length
UINT
Length of the parameter field in bytes: 266
Mode
UINT
Validity (1, 2) - see above (general parameters)
TcsName
-
-
- reserved -
STRING [254]
Name of the telecontrol server that can be resolved by
DNS or IP address as string
RemotePort
UINT
Port of the telecontrol server
Rank
UINT
Priority of the server [1, 2]
1 = first telecontrol server,
2 = second telecontrol server (second server not relevant)
"SMSC"
In STEP 7, the corresponding data can be found in the parameter area "Mobile wireless
communications settings" > "Services and settings".
Table 5- 6
IF_CONF_SMS_Provider
Parameter
Data type
Initial value
Description
Id
UINT
10
ID of the parameter field
Length
UINT
Length of the parameter field in bytes: 28
Mode
UINT
Validity (1, 2) - see above (general parameters)
SMSProvider
STRING [20]
Subscriber number of the SMS center (SMSC) of the
mobile wireless network provider with which the mobile
wireless contract was signed for this station.
"PIN"
In STEP 7, the PIN can be found in the parameter area "Mobile wireless communications
settings" > "Services and settings".
Table 5- 7
IF_CONF_PIN
Parameter
Data type
Initial value
Description
Id
UINT
11
ID of the parameter field
Length
UINT
Length of the parameter field in bytes: 16
Mode
UINT
Validity (1, 2) - see above (general parameters)
Pin
STRING [8]
PIN of the SIM card inserted in the SIM card
The parameter is not relevant if the PIN was correctly
configured. If the PIN was incorrectly configured, the
correct PIN can be entered.