194 / 244
Siemens
Standard application AHU
CE1P3977en_02
Building Technologies
HMI
01.02.2010
17.13 Damper control
17.13.1 Start page
Main Index > Unit > Damper control
Parameter
Function
Value range
Unit
Standard R
S Link
Off delay by fanoff
Delay Off Time for Supply, Exhaust and Fire
damper
0…36000
--- S ---
10
6
Damper
Jumpline to Supply and Exhaust Damper
settings
6
Section:
5.3.1
Fire damper
Actual Command; Jump line to Fire damper
settings
On…Off
6
17.13.2 Damper
Main Index > Unit > Damper Control > Damper
Parameter
Function
Value range
Unit
Standard R
S Link
Outside air cmd
Command Outside air Damper (combined
Damper)
On…Off
X
Outside air fdbk
Outside air Damper Feedback (combined
Damper)
No…Yes
X
Outs offby fdbk alm
Take akway Command in case of Feedback
alarm
No…Yes
Yes
6
StrtUpDly outs fdbk
Delay time until Feedback = 1
0…36000
--- S ---
180
6
Section:
Extract air cmd
Command Extract Damper (combined
Damper)
On…Off
X
5.3.2
Extract air fdbk
Extarct Damper Feedback (combined
Damper)
No…Yes
X
Extr offby fdbk alm
Take akway Command in case of Feedback
alarm
No…Yes
Yes
6
StrtUpDly Extr fdbk
Delay time until Feedback = 1
0…36000
--- S ---
180
6
Opening time
Default Open time for Dampers if no real
Feedback
0…36000
--- S ---
20
6
17.13.3 Fire damper
Main Index > Unit > Damper Control > Fire damper
Parameter
Function
Value range
Unit
Standard R
S Link
Command
Command Fire damper
On…Off
X
Feedback opened
Feedback Damper opened
OK…No
X
Feedback closed
Feedback Damper closed
Ok…No
X
No move
Message if Damper do not follow Command Ok…ALarm
X
State
State of the Fire damper
NDef
Clsd
Move
Opnd
X
Mode
Operation Mode Fire damper
NDef
Ok
Debug
Alm
X
Section:
5.3.3
Opening time
Open Time for Fire damper
0…36000
--- S ---
6
Closing time
Close Time for Fire damper
0…36000
--- S ---
6
Start manual test
Direct start from Auto Test over HMI
Passive
Aktive
Passive
6
Auto Test
Date and Time for Auto Test
6
auto test interval
Interval for Auto Test
0…3600
h
6
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 194