126 / 244
Siemens
Standard application AHU
CE1P3977en_02
Building Technologies
Communication
01.02.2010
Proceed as follows to configure the LON module and connect to the LON bus:
Step Action
1
Controller
OFF
.
2
Connect LON module to controller using plug connection.
3
Connect LON bus cable to LON module (connections CLA and CLB).
4
Controller
ON
:
The module starts / initialization begins.
Communication with the controller and LON bus is active as soon as
the two LEDs "BSP" and "BUS" are steady green.
Caution:
HMI must be reset a second time to update; prior to parame-
terization.
5
The LON card is operational and communicating with the LON network
when both LEDs are green.
6
"Generate" a new account in the LON tool (e.g. NL220, LON Maker).
7
Press service pin on the LON module:
The module is recognized and displayed in the LON tool.
All network variable are available.
8
Issue logical address via the LON tool.
9
Bind the network variable (or use the system integrator via the LON
tool).
After successful LON commissioning via the LON tool, you can access the control-
ler via the LON bus using Saphir Scope.
Main Index > System overview > Communication > Comm module overview >
Module[x] LON
Parameter
Range
Function
State
−
OK.
−
Alarm
Module state.
Comm failure
−
Passive
−
Active
Communication error between module and con-
troller. (e.g. no LON application loaded on the
Neuron Chip).
Location
Displays information that can be set via the LON
chip during bus commissioning.
Application
Name of loaded LON application (list of LON
variable) on the Neuron chip.
Neuron ID
Displays ID number for the Neuron chips.
Send heart beat
Displays current interval for sending values.
Receive heart beat
Displays current interval for receiving values.
Min send intervall
Displays current minimum interval for sending
values. A value may only be sent a maximum of
one time during this interval.
Settings
Go to settings page to parameterize LON mod-
ule.
Software version
Module software version.
Device ID.
Module hardware ID.
Commission LON
module
Note
Parameter
Basis Document Siemens Climatix Control System
BDCX.100820.01GB