
113 / 244
Siemens
Standard application AHU
CE1P3977en_02
Building Technologies
Detail pages: Controller
01.02.2010
Parameter
Range
Function
Status
−
GESP
−
UL
−
LL
−
REG
−
UDEF
Controller status:
−
Controller disabled.
−
Control output = High limit.
−
Control output = Low limit.
−
Control mode.
−
Undefined.
Special settings
Go to Special settings page (at access levels 4
and 2 only).
7.2.2 Special settings
Parameter
Range
Function
Gain
0...1000
−
Amplification factor (KP).
Int action time
0….18000
[s]
Integral action time (Tn).
Min/max limit
-64.0…99.0 [°C] / [% rH]
Adjusts high und Low limits to end position. En-
sures the difference between heating and cool-
ing output in the end position as well as needed.
Min/max limit positiv:
−
Niedrigster Control output clg = Low limit + Min/max limit
−
Niedrigster Control output htg = Low limit
Min/max limit negativ:
−
Niedrigster Control output clg = Low limit
−
Niedrigster Control output htg = Low limit - Min/max limit
Min/max limit positiv:
−
Niedrigster Control output clg = High limit
−
Niedrigster Control output htg = High limit - Min/max limit
Min/max limit negativ:
−
Niedrigster Control output clg = High limit + Min/max limit
−
Niedrigster Control output htg = High limit
High limit = 28
Low limit = 16
Min/max limit = -2
Cooling:
−
Lowest control output clg = Low limit => 16.
−
Lowest control output htg = Low limit - Min/max limit => 16 – 2 = 14.
Heating:
−
Lowest control output htg = High limit + min/max limit => 28 – 2 = 30.
−
Lowest control output htg = High limit => 28.
Function during cooling
Function during heating
Example
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 113