7XV5662-0AD00/DD, 7XV5662-0AD01/DD
English
C53000-B1174-C205-2
73
Climatic Stress Tests
All devices shall be installed so that they are not exposed to direct sunlight, nor subject to
strong fluctuations in temperature that may cause condensation to occur. Storage and
transport with original packing!
Constructive Design
Screw Torque
Continuous Shock IEC
60255-21-2, Class 1
IEC 60068-2-29
Semi-sinusoidal
10 g acceleration, duration 16 ms, each 1000 0160 shocks
in both directions of the 3 axes
Temperatures
IEC 60068-2
recommended temperature range for
operation
-10
°C to +55 °C (+14°F to +131 °F)
permitted temperature range for operation
-25 °C to +55 °C (-13 °F to +131 °F)
recommended temperature range during
storage
+10 °C to +35 °C (+50 °F to +95 °F)
permitted temperature range during storage -40 °C to +85 °C (-40 °F to +185 °F)
permitted temperature range during trans-
port
-40 °C to +85 °C (-40 °F to +185 °F)
Humidity
Admissible humidity conditions
=
75 % relative humidity, on 56 days of the
year up to 93 % relative humidity, conden-
sation must be avoided!
Case
Measurements
188 mm × 120 mm × 55 mm (W × D× H)
Weight
0.8 kg (1.8 lb)
Degree of protection
According to EN 60529
Mounting housing
IP 41
Interface side
IP 2x
Terminal screw
0.4 Nm to 0.5 Nm
Grounding screw
1.2 Nm