English
7XV5662-0AD00/DD, 7XV5662-0AD01/DD
70
C53000-B1174-C205-2
Electrical Tests
Insulation Test
Isolation coordination according to IEC / EN / UL 60950-1 overvoltage category II, pollution
degree 2.
Isolation coordination according to IEC / EN 60255-27 overvoltage category III, pollution
degree 2.
Isolation coordination according to IEC / EN / UL 61010-1 overvoltage category III, pollution
degree 2.
EMC Tests for Noise Emission
Regulations
IEC 60950-1
for more standards see also individual
functions
In-/outputs
Insulation
Voltage range
test voltage
Impulse vol-
tage
auxiliary voltage
double insulation
300 V
3.51 kV
5 kV
relais contact
couble insulation
300 V
3.51 kV
5 kV
G.703.1 E1/T1
Basic insulation
< 10 V
1.5 kV
1 kV
Standard
IEC/EN 61000-6-2 , IEC 60255 -26,
(product standards)
VDE 0435
IEEE Std C37.90.0/.1/.2
For more standards see also individual
functions
1 MHz test, IEC 60255-26,
IEC 61000-4-18 Class III, IEEE C37.90.1
2.5 kV (Peak), 1 MHz,
= 15
μ
s, 400 Surges
per s, Test duration 60 s, Ri = 200
Ω
Electrostatic discharge,
IEC 60255-26, IEC 61000-4-2 Class IV
8 kV contact discharge, 15 kV air discharge,
both polarities, 150 pF, Ri = 330
Ω
Radio frequency electromagnetic field,
amplitude-modulated,
IEC 60255-26, IEC 61000-4-3 Class III
10 V/m, 80 MHz to 2.7 GHz 80 % AM,
1 kHz