EMC Tests for Noise Emission (Type Test)
Fast transient bursts,
IEC 60255-26, IEC 61000-4-4 Class IV,
IEEE C37.90.1
4 kV, 5 ns/50 ns, 5 kHz
Burst length = 15 ms
Repetition rate 300 ms, both polarities
Ri = 50
Ω
, test duration1 min
High energy surge voltages (SURGE),
IEC 60255-26, IEC 61000-4-5
Impulse: 1.2
μ
s/50
μ
s, 10
μ
s/700
μ
s
Auxiliary voltage
Common mode: 2 kV, 12
Ω
, 9
μ
F
Diff. mode:1 kV, 2
Ω
, 18
μ
F
Relay outputs
Common mode: 4 kV, 42
Ω
, 0.5
μ
F
Communication port: RS232/RS485
Common mode: 2 kV, 2
Ω
, 18
μ
F
Communication port: E1/T1
Common mode:
(1.2
μ
s/50
μ
s) 4 kV, 2
Ω
, 18
μ
F
(1.2
μ
s/50
μ
s) 4 kV, 2
Ω
, 18
μ
F
HF on lines, amplitude-modulated,
IEC 60255-26
IEC 61000-4-6 Class III
10 V, 150 kHz to 80 MHz, 80 % AM, 1 kHz
Power system frequency magnetic field
IEC 61000-4-8, Class IV
IEC 60255-26
30 A/m continious, 300 A/m for 3 s
Damped oscillatory wave
IEC 61000-4-18
2.5 kV (Peak), 100 kHz, 40 pulses per s,
Test duration 60 s, Ri = 200
Ω
Radiated Electromagnetic Interference
IEEE Std C37.90.2
20 V/m, 80 MHz to 1 GHz, 80 % AM
35 V/m, 80 MHz bis 1 GHz, 100 % PM
Standard
IEC/EN 61000-6-4
Radio noise voltage to lines, only auxiliary
voltage IEC-CISPR 11
150 kHz to 30 MHz limit class A
Interference field strength IEC-CISPR 11
30 MHz to1000 MHz limit classA