7SG12 DAD N Relay Settings
©2010 Siemens Protection Devices Limited
Chapter 3 Page 10 of 20
Description Range
Default
Setting
Aux I/P 13 Operated
1
NONE,
1…32
NONE
Aux I/P 14 Operated
1
NONE,
1…32
NONE
Aux I/P 15 Operated
1
NONE,
1…32
NONE
Aux I/P 16 Operated
1
NONE,
1…32
NONE
Aux I/P 17 Operated
1
NONE,
1…32
NONE
Aux I/P 18 Operated
1
NONE,
1…32
NONE
Aux I/P 19 Operated
1
NONE,
1…32
NONE
Self Reset LEDs
LEDs selected, as Self Reset will
automatically reset when the driving
signal is removed. By default all LEDs
are Hand Reset and must be manually
reset either locally via the front fascia or
remotely via communications.
NONE, 1…32
1
1) Only when fitted.
1.11 Data Storage Menu
Description Range
Default
Setting
Clear Faults
Clears the fault recorder
NO, YES
NO
Clear Events
Clears the event recorder
NO, YES
NO
Pre-Trigger Storage
Pre-trigger storage is that percentage of
the waveform record that is recorded
prior to the waveform recorder being
triggered
10…90 %
20 %
Data Record Duration
1
Selects the length of time for each
waveform record
5 Recs x 1 Seconds, 2 Recs
x 2 Seconds, 1 Recs x 5
Seconds
5 Recs x 1 Second
Trigger Waveform
Triggers the waveform recorder
NO, YES
NO
Clear Waveforms
Clears the waveform recorder
NO, YES
NO
1) Number of records and duration available is dependent upon relay model
1.12 Communications Menu
Description Range
Default
Setting
Station Address
IEC 60870-5-103 Station Address
0…254 0
COM1 Protocol
Selects protocol to use for COM 1
OFF, IEC60870-5-103,
MODBUS-RTU
IEC60870-5-103
COM1 Baud Rate
Sets the communications baud rate for
com port 1 (Rear upper Fibre optic port)
75, 110, 300, 600, 1200,
2400, 4800, 9600, 19200,
38400, 57600, 115200
19200
COM1 Parity
Selects whether parity information is
used
Even, Odd, None
Even
COM1 Line Idle
Selects the communications line idle
sense
Light Off, Light On
Light Off
COM1 Data Echo
Enables echoing of data from RX port to
TX port when operating relays in a Fibre
Optic ring configuration
Off, On
Off
COM2 Protocol
Selects protocol to use for COM 2
OFF, IEC60870-5-103,
MODBUS-RTU, ASCII
ASCII
COM2 Baud Rate
Sets the communications baud rate for
com port 2 (Rear lower Fibre optic port
AND Front Fascia RS232 port)
75, 110, 300, 600, 1200,
2400, 4800, 9600, 19200,
38400, 57600, 115200
57600
COM2 Parity
Selects whether parity information is
Even, Odd, None
Even