Parameterizing
7.2 Parameterizing via the operator interface
PAC1020
60
Equipment Manual, 05/2020, L1V30610008B-01
7.2.9.2
Resetting
Selection
Range
Factory
setting
CLEAR MIN/MAX VALUES
Resets all minimum and maximum values to the
instantaneous value.
•
Yes: active
•
No: not active
No: not active
FACTORY DEFAULTS
All device settings and measured values except
the communication parameters and energy sec-
ondary values are reset to the as-delivered state.
•
Yes: active
•
No: not active
No
COMMUNICATION
PARAMETERS
All communication settings are reset to the as-
delivered state.
•
Yes: active
•
No: not active
No
EXECUTE
Confirmation of the reset
–
Note
The reset must be confirmed by selecting the "EXECUTE" field. Otherwise the device reset is
not executed.