
Parameterizing
7.2 Parameterizing via the operator interface
PAC1020
52
Equipment Manual, 05/2020, L1V30610008B-01
7.2.3
Basic parameters
Measuring inputs can be parameterized in the "BASIC PARAMETERS" menu item.
Voltage input
Selection
Range
Factory
setting
CONNECTION TYPE
Selection of connection type
•
3P4W:
3 phases, 4 conductors
•
3P3W:
3 phases, 3 conductors
3P4W
USE PTs
•
ON:
Measurement using voltage transformers.
When measuring via voltage transformers, the
device must know the voltage transformation
ratio. For this purpose, the primary and sec-
ondary voltages must be specified in the fields
"PT PRIMARY" and "PT SECONDARY".
When changing from direct measurement to
measurement using voltage transformers, the
device accepts the last set reference measur-
ing voltage as the secondary voltage and as
the primary voltage.
•
OFF:
Measurement directly on the low-voltage sys-
tem.
When changing from measurement using
voltage transformers to direct measurement,
the device accepts the last set secondary volt-
age as the reference measuring voltage.
OFF
PT PRIMARY
(USE PTs ON)
1 … 999999 V, freely adjustable
400 V
PT SECONDARY
(USE PTs ON)
1 … 400 V, freely adjustable
400 V
Summary of Contents for 7KM1020-0BA01-1DA0
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC1020 6 Equipment Manual 05 2020 L1V30610008B 01 ...
Page 22: ......
Page 50: ...Operation 6 1 Device interface PAC1020 48 Equipment Manual 05 2020 L1V30610008B 01 ...
Page 77: ...Technical data 10 1 Labeling PAC1020 Equipment Manual 05 2020 L1V30610008B 01 75 ...
Page 78: ......
Page 93: ......
Page 94: ......