
Connection
4.3 Connection examples
PAC1020
34
Equipment Manual, 05/2020, L1V30610008B-01
6.
3-phase measurement, 3 conductors, unbalanced load, with voltage transformer, with
2 current transformers
Connection type 3P3W
*
The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
**
Connection of supply voltage
*** Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-7
Connection type 3P3W, with voltage transformer, with 2 current transformers
7.
2-phase measurement, 4 conductors, unbalanced load, without voltage transformer,
with 2 current transformers
Connection type 3P4W
*
The fuses are only used for cable protection.
All commercially available miniature circuit breakers up to 20 A (C) can be used.
**
Connection of supply voltage
*** Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-8
Connection type 3P4W, without voltage transformer, with 2 current transformers
See also
Measuring inputs (Page 13)
Summary of Contents for 7KM1020-0BA01-1DA0
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC1020 6 Equipment Manual 05 2020 L1V30610008B 01 ...
Page 22: ......
Page 50: ...Operation 6 1 Device interface PAC1020 48 Equipment Manual 05 2020 L1V30610008B 01 ...
Page 77: ...Technical data 10 1 Labeling PAC1020 Equipment Manual 05 2020 L1V30610008B 01 75 ...
Page 78: ......
Page 93: ......
Page 94: ......