Connection
4.1 Safety instructions
PAC1020
28
Equipment Manual, 05/2020, L1V30610008B-01
Permissible nominal voltage and tolerance for each of the connection types
Line supply systems and nominal voltages
Three-phase four-
wire systems
a)
with grounded
neutral conductor
TT system
TN-C-S system
Three-phase four-
wire systems
a)
with ungrounded
neutral conductor
(IT systems)
b, c)
Three-phase three-
wire systems
ungrounded
Three-phase three-
wire systems
with grounded
phase
Single-phase two-
wire systems
AC or DC
Split-phase (single-
phase three-wire)
systems
a)
AC or DC
230 / 400 V
(+20 %)
230 / 400 V
(+20 %)
400 V
(+20 %)
230 V
(+20 %)
230 V
(+20 %)
230 / 460 V
(+20 %)
a)
The two voltage values that are separated by a forward slash (/) stand for the phase-to-neutral (or line-to-neutral) volt-
age, followed by the voltage between the phases (or line-to-line). For example, "230 / 400" means that the voltage be-
tween any phase and the neutral conductor is 230 V and the voltage between any phase and another phase is 400 V.
Similarly, "230 / 460" means that the voltage between each phase and the neutral conductor is 230 V and the voltage be-
tween the two phases is 460 V.
b)
Z is an impedance (usually 1500
Ω) that can be connected between the neutral conductor and ground.
c)
If the insulation is monitored, the neutral conductor is considered to be grounded.
Excerpt from DIN EN 61010-1 (VDE 0411-1): 2020-03
Summary of Contents for 7KM1020-0BA01-1DA0
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC1020 6 Equipment Manual 05 2020 L1V30610008B 01 ...
Page 22: ......
Page 50: ...Operation 6 1 Device interface PAC1020 48 Equipment Manual 05 2020 L1V30610008B 01 ...
Page 77: ...Technical data 10 1 Labeling PAC1020 Equipment Manual 05 2020 L1V30610008B 01 75 ...
Page 78: ......
Page 93: ......
Page 94: ......