Parameterizing
7.2 Parameterizing via the operator interface
PAC1020
54
Equipment Manual, 05/2020, L1V30610008B-01
7.2.4
Integrated I/Os
Device settings for using the digital inputs and outputs.
Digital output
Selection
Range
Factory
setting
DIG. OUTPUT
One digital output is available:
•
0.0
–
ACTION
•
OFF:
Output is deactivated.
•
REMOTE OUTPUT:
Output is controlled by remote access.
•
PULSE: Output issues the parameterized num-
ber of pulses or edges per energy unit.
OFF
PULSES
Number of pulses to be issued per unit. The refer-
ence unit is defined in the "UNIT" field.
1 … 4000
1
UNIT
(with PULSE only)
Selects the type of cumulated power (active ener-
gy or reactive energy):
•
kWh IMPORT
•
kWh EXPORT
•
kvarh IMPORT
•
kvarh EXPORT
The import values at which a pulse is output are
defined in the fields "UNIT" and "PER" (pulses per
unit).
Value of the cumulated power for which a config-
urable number of pulses is output. The number of
pulses to be output is defined in the field "PER".
•
1 kVarh or kW
•
10 kVarh or kW
•
100 kVarh or kW
•
1000 kVarh or kW
kWh IMPORT