Connecting 
3.1 Wiring and block diagram 

Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0) 

16

 

Manual, 03/2019, A5E45488510-AA 

Wiring: 2-wire and 3-wire connection in DI operating mode 

The example in the following figure shows the terminal assignment of the IO-Link 

Master CM 8xIO-Link communication module in DI operating mode. 

Reverse polarity protection

U

Sn

 

Supply voltage (positive) 

Backplane bus interface

RUN 

Status display LED (green) 

IO-Link circuitry

ERROR  Error display LED (red) 

Sensor, 3-wire connection

PWR 

Power LED (green) 

Sensor, 2-wire connection

C/Qn 

Port n 

Ground 

C

n

 

Port status/channel error LED (green/red) 

L+  Supply voltage 24 V DC 

Q

n

 

LED channel status in standard DI mode 

(green) 

Figure 3-2 

Terminal assignment for 2-wire and 3-wire connection in DI operating mode 

Summary of Contents for 6ES7547-1JF00-0AB0

Page 1: ......

Page 2: ...__________________ ___________________ SIMATIC S7 1500 ET 200MP Communication module IO Link Master CM 8xIO Link 6ES7547 1JF00 0AB0 Manual 03 2019 A5E45488510 AA Preface Documentation guide 1 Product overview 2 Connecting 3 Parameters address space 4 Diagnostic alarms 5 Technical specifications 6 Dimensional drawing 7 Parameter data record A ...

Page 3: ...ly by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens prod...

Page 4: ...he system manual and the function manuals enables you to commission the ET 200MP distributed I O system Conventions Please also observe notes marked as follows Note A note contains important information on the product described in the documentation on the handling of the product or on the section of the documentation to which particular attention should be paid Recycling and disposal For environme...

Page 5: ...please visit https www siemens com industrialsecurity Siemens products and solutions undergo continuous development to make them more secure Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used Use of product versions that are no longer supported and failure to apply the latest updates may increase customers exposu...

Page 6: ...n module 12 2 4 Reset communication module to factory settings 13 3 Connecting 14 3 1 Wiring and block diagram 14 4 Parameters address space 17 4 1 Parameters 17 4 2 Declaration of parameters 19 4 3 Address space 21 5 Diagnostic alarms 26 5 1 Status and error displays 26 5 2 Diagnostic alarms 29 6 Technical specifications 31 7 Dimensional drawing 34 7 1 Dimensional drawing 34 A Parameter data reco...

Page 7: ...configuration and programming Device information Product manuals contain a compact description of the module specific information such as properties wiring diagrams characteristics and technical specifications General information The function manuals contain detailed descriptions on general topics regarding the SIMATIC S7 1500 and ET 200MP systems e g diagnostics communication motion control Web s...

Page 8: ...nal library in the Documentation area In addition your data is already filled out in support requests and you can get an overview of your current requests at any time You must register once to use the full functionality of mySupport You can find mySupport on the Internet https support industry siemens com My ww en mySupport Documentation In the Documentation area in mySupport you can combine entir...

Page 9: ...election tool SIMATIC Automation Tool You can use the SIMATIC Automation Tool to perform commissioning and maintenance activities simultaneously on various SIMATIC S7 stations as a bulk operation independent of the TIA Portal General function overview Network browsing and creation of a table showing the accessible devices in the network Flashing of device LEDs or HMI display to locate a device Dow...

Page 10: ...ctive dimensioning of your PROFINET installation as early as in the planning stage In addition SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves This helps to prevent problems in commissioning or failures during productive operation even in advance of a planned operation This increases the availability of the production pla...

Page 11: ...ew of the IO Link Master CM 8xIO Link communication module Properties The module has the following technical properties IO Link master according to IO Link specification V1 1 Communication module with 8 ports channels Data transmission rate COM1 4 8 kbaud COM2 38 4 kbaud COM3 230 4 kbaud Standard DI mode Suitable for connecting up to eight IO Link devices 3 wire connection or eight standard encode...

Page 12: ... S7 PCT Variable address range of I O data with up to 240 byte inputs and 240 byte outputs Master Backup with function block IO_LINK_MASTER Port Qualifier Information PQI I M 0 to 3 The module can be used with the following engineering tools Table 2 1 Engineering tools Firmware version of the module S7 PCT STEP 7 TIA Portal GSD file V1 0 in CPU PROFINET PROFIBU S station As of V3 5 SP1 As of V15 1...

Page 13: ...8 function block is used to read all relevant IO Link device and IO Link Master parameters The parameters can be stored retentively at a central location such as in a data block in the IO controller The status of the IO Link devices or IO Link ports stored in the IO Link Master can be restored with the IO_LINK_MASTER_8 function block As a result the IO Link ports and the IO Link Master are configu...

Page 14: ...7 PCT to the factory state After a Reset to factory settings the parameters of the IO Link Master CM 8xIO Link communication module are assigned as follows The ports are in DI mode The ports are mapped to the relative addresses 0 0 0 7 The PortQualifier is disabled I M data 1 to 3 is deleted Note The master backup of the IO Link Master is deleted and the delivery condition is restored You should r...

Page 15: ...terminal assignments for 3 wire and 5 wire connection of IO Link devices or 2 wire and 3 wire connection in DI operating mode You can use and combine the different wiring options for all channels Ensure that all devices are connected to the SELV PELV power supply or equivalent NOTICE Internal transducer supply Use only the supply voltage USn M made available by the IO Link Master CM 8xIO Link comm...

Page 16: ...Link 3 and 5 conductor connection of IO Link devices Reverse polarity protection USn Supply voltage positive Backplane bus interface RUN Status display LED green IO Link circuitry ERROR Error display LED red Device 3 wire connection PWR Power LED green Device 5 wire connection C Qn Port n M Ground Cn Port status channel error LED green red L Supply voltage 24 V DC Qn LED channel status in standard...

Page 17: ... Link communication module in DI operating mode Reverse polarity protection USn Supply voltage positive Backplane bus interface RUN Status display LED green IO Link circuitry ERROR Error display LED red Sensor 3 wire connection PWR Power LED green Sensor 2 wire connection C Qn Port n M Ground Cn Port status channel error LED green red L Supply voltage 24 V DC Qn LED channel status in standard DI m...

Page 18: ...tings of the parameters are marked in bold in the Value ranges column Table 4 1 General parameters GSD file Parameters Value range Effective range Diagnostics Diagnostics No supply voltage L Disable Enable Module Diagnostics Port Disable Enable Port channel Master parameter Port Qualifier Information PQI Disable Enable Module Port configuration without S7 PCT Disable Enable Module The following ta...

Page 19: ... Stor age Identical type V1 0 without Backup Restore Type compatible V1 1 with out Backup Restore Type compatible V1 1 with Backup Restore Type compatible V1 1 with Restore Type compatible V1 1 with Backup Restore If PQI is activated 1 byte less space remains for input data of the device For example GSD setting 16 bytes 15 bytes PQI Make sure not to exceed the maximum possible length of the input ...

Page 20: ...description of the utilized IO Link device Port Qualifier Information This parameter releases the Port Qualifier Information PQI The PQI provides information on the port status and the IO Link device status Port configuration without S7 PCT This parameter enables the port configuration without S7 PCT for the module Operating mode This parameter determines the mode in which you operate the selected...

Page 21: ...need to configure the Device ID Vendor ID to enable this You need to store the Vendor ID and Device ID of the connected IO Link device in STEP 7 In addition you can select the inspection level for data storage Identical type V1 0 without Backup Restore Type compatible V1 1 without Backup Restore Type compatible V1 1 with Backup Restore Type compatible V1 1 with Restore You can find instructions fo...

Page 22: ...55 5 DP ST S7 1500 CPU 8 byte inputs 8 byte outputs X X X X X 16 byte inputs 0 byte outputs X X X X X 16 byte inputs 16 byte outputs X X X X X 24 byte inputs 16 byte outputs X X X X X 32 byte inputs 32 byte outputs X X X X X 40 byte inputs 32 byte outputs X X X X 64 byte inputs 64 byte outputs X X X X 72 byte inputs 64 byte outputs X X X 128 byte inputs 128 byte outputs X X X 136 byte inputs 128 b...

Page 23: ...ponding GSD file You can find this for download on the Internet https support industry siemens com cs ww en view 80206700 Port configuration CPU With an IO Link Master CM 8xIO Link you can commission the IO Link ports of the IO Link Master or the connected IO Link devices in two different ways Port configuration with STEP7 or GSD without S7 PCT Port configuration with S7 PCT Port configuration wit...

Page 24: ...Port Configuration Tool S7 PCT V3 5 SP1 or higher In doing so select the IO Link device from the device catalog of S7 PCT and assign the device to an IO Link port Port Qualifier Information PQI You can activate the Port Qualifier Information PQI for your IO Link Master Note Port Qualifier Information PQI If you have activated the Port Qualifier Information PQI it is always transferred with the siz...

Page 25: ...available 1 IO Link device is in the Preoperate or Operate state Device error 0 No error 1 An error or warning has occurred Port Qualifier 0 IO data is not valid 1 IO data is valid Position of the PQI byte in the process image example Figure 4 2 Address space IO Link Master In the example above 16 bytes are set for port 1 the IO Link device transfers the data in bytes 0 to 7 and the PQI byte is se...

Page 26: ...gure shows the assignment of the address space of a port for the IO Link Master CM 8xIO Link if you have configured the port as a digital input Figure 4 3 Address space of the inputs of the IO Link Master CM 8xIO Link in standard DI mode Reference You can find additional information in the IO Link System https support automation siemens com WW view en 65949252 function manual ...

Page 27: ... displays LED display Cn Port status channel error Qn Channel status in standard DI mode PWR Supply voltage L n Channel number Figure 5 1 LED display Meaning of the LED displays The following tables show the meaning of the status and error displays Remedial measures for diagnostic alarms can be found in the Diagnostic alarms Page 29 chapter ...

Page 28: ...ectors are inserted Check whether too many modules are inserted Flashes Off The module starts up and flashes until the valid parameter assignment is set On Off Module parameters are assigned On Flashes Indicates module errors at least one error is present on one channel e g wire break Evaluate the diagnostics and eliminate the error e g wire break Flashes Flashes The hardware is defective Replace ...

Page 29: ... green The port is in IO Link mode the device is not connected or the port is not connected with the configured device On green Port in IO Link mode device not connected On red Wire break or short circuit to ground Supply voltage L missing or too low IO Link device error Qn LEDs Valid for the IO Link port that is in standard DI mode Table 5 4 Status displays of LEDs Q1 to Q8 Q1 to Q8 Meaning Off P...

Page 30: ...H 5112H X Overvoltage 3H Supply voltage too high 5110H X Overheating 5H Temperature exceeded on master 1805H X Temperature exceeded on device 4000H 4210H X Wire break 6H No IO Link device connected There is a break in the signal line to the IO Link device IO Link device cannot communicate due to another error 1800H X Overflow 7H Process tag range exceeded 8C10H Measuring range exceeded 8C20H X Und...

Page 31: ...e too low 20 V 1890H L supply voltage for device missing 1806H L supply voltage for device too low 20 V 1807H X Defective fuse 12H Fuse on device is defective 5101H X Safety shutdown 19H Serious error master has to be replaced 1880H X External fault 1 AH Error in data storage 1809H 180AH 180BH 180CH 180DH More than 6 errors are pending simultaneously on the IO Link device 1808H Consistency error i...

Page 32: ...s of version V15 1 with HSP 274 STEP 7 configurable integrated as of ver sion Configurable via GSD file PROFIBUS as of GSD version GSD revi sion GSD as of Revision 5 PROFINET as of GSD version GSD revi sion GSDML V2 34 Supply voltage Rated value DC 24 V permissible range lower limit DC 20 4 V permissible range upper limit DC 28 8 V Reverse polarity protection Yes Input current Current consumption ...

Page 33: ...th unshielded max 20 m Operating modes IO Link Yes DI Yes DQ No Time Based IO TIO IO Link IN No TIO IO Link OUT No TIO IO Link IN OUT No Connection of IO Link devices Port type A Yes Port type B Yes 24 V DC via external terminal Interrupts diagnostics status information Alarms Diagnostic alarm Yes The port diagnosis is available in the IO Link mode only Diagnostic messages Monitoring the supply vo...

Page 34: ... installation min 0 C horizontal installation max 60 C Observe derating vertical installation min 0 C vertical installation max 40 C Observe derating Dimensions Width 35 mm Height 147 mm Depth 129 mm Power reduction derating to total current of outputs per module The following derating curves show the load capacity of the transducer supply outputs in relation to the mounting position and the ambie...

Page 35: ... 1 Dimensional drawing The dimensional drawing of the module on the mounting rail as well as a dimensional drawing with open front panel are provided in the appendix Always observe the specified dimensions for installation in cabinets control rooms etc Figure 7 1 Dimensional drawing of the IO Link Master CM 8xIO Link module ...

Page 36: ...Dimensional drawing Communication module IO Link Master CM 8xIO Link 6ES7547 1JF00 0AB0 Manual 03 2019 A5E45488510 AA 35 Figure 7 2 Dimensional drawing of the IO Link Master CM 8xIO Link module side view with open front cover ...

Page 37: ...U by this action This means the parameters set in STEP 7 are still valid after a restart Output parameter STATUS If errors occur when transmitting parameters with the WRREC instruction the module continues operation with the previous parameter assignment The STATUS output parameter contains a corresponding error code You will find a description of the WRREC instruction and the error codes in the S...

Page 38: ...t Communication module IO Link Master CM 8xIO Link 6ES7547 1JF00 0AB0 Manual 03 2019 A5E45488510 AA 37 Structure of data record 128 Figure A 1 Structure of data record 128 Header information The figure below shows the structure of the header information Figure A 2 Header information ...

Page 39: ...unication module IO Link Master CM 8xIO Link 6ES7547 1JF00 0AB0 38 Manual 03 2019 A5E45488510 AA IO Link start parameters The following figure shows the structure of the IO Link start parameter Activate a parameter by setting the corresponding bit to 1 Figure A 3 IO Link start parameters ...

Page 40: ...A 39 Port parameter The following figure shows an extract from the structure of the port parameter Activate a parameter by setting the corresponding bit to 1 If you have selected IO Link Manual operating mode you must enter the Vendor ID byte x 5 and x 6 and Device ID byte x 7 to x 10 yourself You can find the Vendor ID and Device ID in the IODD of the IO Link device being used ...

Page 41: ...meter data record A 1 Parameter assignment and structure of parameter data set Communication module IO Link Master CM 8xIO Link 6ES7547 1JF00 0AB0 40 Manual 03 2019 A5E45488510 AA Figure A 4 Port parameter ...