Technical specifications
Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0)
32
Manual, 03/2019, A5E45488510-AA
Article number
6ES7547-1JF00-0AB0
IO-Link protocol 1.1
Yes
Cycle time, min.
2 ms
Size of process data, input per port
33 byte; max.
Size of process data, input per module
240 byte; max.
Size of process data, output per port
32 byte; max.
Size of process data, output per module
240 byte; max.
Memory size for device parameter
2 kbyte; for each port
Master backup
Yes
Configuration without S7-PCT
Yes
Cable length unshielded, max.
20 m
Operating modes
•
IO-Link
Yes
•
DI
Yes
•
DQ
No
Time Based IO
– TIO IO-Link IN
No
– TIO IO-Link OUT
No
– TIO IO-Link IN/OUT
No
Connection of IO-Link devices
•
Port type A
Yes
•
Port type B
Yes; 24 V DC via external terminal
Interrupts/diagnostics/status information
Alarms
•
Diagnostic alarm
Yes; The port diagnosis is available in the IO-Link
mode only.
Diagnostic messages
•
Monitoring the supply voltage
Yes
•
Wire-break
Yes
•
Short-circuit
Yes
•
Group error
Yes
Diagnostics indication LED
•
Monitoring of the supply voltage (PWR-
LED)
Yes; Green LED
•
Channel status display
Yes; Green LED
•
for channel diagnostics
Yes; Red LED
•
for module diagnostics
Yes; Red LED
Potential separation
Potential separation channels
•
between the channels
No