Product overview
2.1 Properties
Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0)
Manual, 03/2019, A5E45488510-AA
11
●
Configurable diagnostics can be set for each channel
●
Automatic backup of the device parameters during replacement of the IO-Link device
(only for V1.1 devices)
●
Configuration limits:
– Max. 32 bytes input and output data per port
– Max. 240 bytes input and output data per module
The module supports the following functions:
●
Firmware update
●
Identification and maintenance data (I&M)
●
IO-Link port configuration with S7-PCT
●
IO-Link port configuration with STEP7 or GSD (without S7-PCT)
●
Variable address range of I/O data with up to 240 byte inputs and 240 byte outputs
●
Master Backup with function block IO_LINK_MASTER
●
Port Qualifier Information (PQI)
●
I&M 0 to 3
The module can be used with the following engineering tools:
Table 2- 1
Engineering tools
Firmware version of the
module
S7-PCT
STEP 7 (TIA Portal)
GSD file
V1.0 (in
CPU/PROFINET/PROFIBU
S station)
As of V3.5 SP1
As of V15.1
X
Accessories/spare parts
The following accessories/spare parts are available for the module and can also be ordered
separately:
●
Labeling strips
●
U connector
●
Universal front cover
Additional information
You can find more information on accessories in the ET 200MP Distributed I/O System
https://support.industry.siemens.com/cs/ww/en/view/59191792
) system manual in the
Accessories/Spare parts section.
Summary of Contents for 6ES7547-1JF00-0AB0