Parameters/address space
4.3 Address space
Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0)
22
Manual, 03/2019, A5E45488510-AA
The following table provides an overview of the maximum address spaces for the respective
interface modules.
IM
Firmware version
Max. address space
per station
Max. address space
per module
IM 155-5 PN BA
V4.0.2
64 bytes
64 bytes
IM 155-5 PN ST
V4.1.0
512 bytes
256 bytes
IM 155-5 PN HF
V3.0.1
512 bytes
256 bytes
IM 155-5 DP ST
V3.0.0
244 bytes
32 bytes
Note
IO-Link Master behind an IM 155-5 DP ST
In connection with an IM 155-5 DP ST, you configure the IO-Link master exclusively using a
GSD file. Install the corresponding GSD file. You can find this for download on the Internet
https://support.industry.siemens.com/cs/ww/en/view/80206700
Port configuration CPU
With an IO-Link Master CM 8xIO-Link, you can commission the IO-Link ports of the IO-Link
Master or the connected IO-Link devices in two different ways:
●
Port configuration with STEP7 or GSD (without S7-PCT)
●
Port configuration with S7-PCT
Port configuration with STEP7 or GSD (without S7-PCT)
Requirements
You have selected the "Port configuration without S7-PCT" check box in the configuration of
the IO-Link master in STEP 7.
Procedure
You configure the IO-Link master directly in STEP 7:
●
Activate the diagnostics
●
Configuration of the I/O data lengths for each port
●
Activating the Port Qualifier Information (PQI)
●
Port mode:
– Operation in "IO-Link Autostart" mode (default)
– Operation in "IO-Link Manual" mode
– Operated as DI
– Deactivated