Fig. 11. 

Rack-type mounting in a 19” cabinet with PDU.

5.1.5.8.  Preliminary considerations before connection.

 

In the description of this manual, reference is made to the 

connection of terminals and switch operations that are 

only available in some versions or devices with extended 

backup. Ignore the related operations if your unit does not 

feature them.

 

Thermal control of these devices is carried out with the 

passage of forced air from the front to the rear.

The front surface and about 15 cm on the rear side should 

be left free of obstructions to facilitate the free circulation 

of air for ventilation.

 

Follow and respect the instructions described in this section 

referring to the installation of a single device or a system 

in parallel.

 

Protection or external manual bypass board:

 

ˆ

The system will have at least one short-circuit 

protection on the UPS’s power supply line.

 

ˆ

It is advisable to have an external manual bypass board 

fitted with input, output and manual bypass protections 

in single systems.

 

ˆ

For parallel systems, 

it is essential

 to have a 

distribution or manual bypass board. The board’s 

circuit breakers must be able to isolate a UPS from 

the system in the event of a fault and power the loads 

with the others, either during periods of preventative 

maintenance or during breakdown and repair.

 

Upon request, we can supply an external manual bypass 

board for a single device or parallel system.

You can also choose to manufacture it, taking into account 

the version and configuration of the device or system 

available and the documentation contained in the CD-ROM 

or pen drive relating to ‘Recommended installation’.

 

In the documentation supplied with this user manual 

and/or on the CD-ROM or pen drive, information is 

available on ‘Recommended installation’ for each input and 

output configuration. This documentation includes wiring 

diagrams and information about the sizes of the protections 

and the minimum cross sections of cables connected to the 

device according to their rated working voltage. All values   

are calculated for a 

maximum total cable length of 30 m

 

between the distribution board, equipment and loads.

 

ˆ

For longer lengths correct the cross sections to avoid 

voltage drops, respecting the regulations or standards 

corresponding to the country.

 

ˆ

In the same documentation and for each configuration, 

information for ‘N’ units in parallel, as well as backfeed 

protection characteristics, is available.

 

In parallel systems, the length and cross section of 

the cables that run from the distribution or manual 

bypass board to each UPS and from these to the board will 

be the same for all of them without exception.

 

The cross section of the cables must always be considered 

in relation to the size of the terminals of the switches, so 

that they are correctly fastened across their entire cross 

section for optimum contact between the two elements.

 

Only rated currents are printed on the nameplate of the 

equipment as indicated by the EN-IEC 62040-1 safety 

standard. For the calculation of the input current, the power 

factor and the equipment's own performance have been 

considered.

Overload conditions are considered a non-permanent 

and exceptional working mode, and will not be taken 

into account in the application of the protections. Do not 

connect appliances or devices which may overload the UPS 

to the terminals and/or outlets, such as motors.

 

If peripheral input, output or bypass elements such as 

transformers or autotransformers are added to the UPS or 

parallel system, the currents indicated on the nameplates of 

these elements must be taken into consideration in order to 

use the appropriate cross sections, in compliance with local 

and/or national Low Voltage Electrotechnical Regulations.

 

When a galvanic isolation transformer is added to a UPS 

or parallel system as an optional extra, as standard or 

independently, either on the input line, at the output or 

both, it must be fitted with protection against indirect 

contact (differential circuit breaker) at the output of each 

transformer, since, due to its own insulation properties, it 

will prevent the tripping of the protections placed on the 

primary of the isolation transformer in case of electric shock 

on the secondary (output of the isolation transformer).

 

We remind you that all the isolation transformers installed 

or factory supplied, have the output neutral grounded 

through a bridge between the neutral terminal and ground. 

If the isolated output neutral is required, this bridge must be 

removed, taking the precautions indicated in the respective 

local and/or national low voltage regulations.

 

This device is suitable for installation in networks 

with TT, TN-S, TN-C or IT power distribution 

systems, taking into account at the time of installation the 

particularities of the system used and the national electrical 

regulations of the destination country.

 

The SLC TWIN RT2 features terminals for the installation 

of an external emergency power off button (EPO) or, failing 

that, a single device must be installed to cut the power 

supply to the loads in any operating mode.

5.1.5.9.  Preliminary considerations before connection, regarding 

the batteries and their protections.

 

SLC TWIN RT2 devices from 0.7 to 3 kVA incorporate the 

batteries in the same box as the device, except for B0, B1 

and higher power models.

 

The battery protection of the device and of any accumulator 

module is always by means of internal fuses that are not 

accessible to the user.

USER MANUAL        

 

 

 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 

Summary of Contents for SLC TWIN RT2 LION

Page 1: ...SLC TWIN RT2 0 7 10 kVA UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL Industriestrasse 17 Tel 061 926 90 60 www sicotec ch CH 4415 Lausen Fax 061 926 90 66 usv sicotec ch SICOTEC AG...

Page 2: ...ower typemountingwithPDU 5 1 5 7 Rackmountingin19 cabinetwithPDU 5 1 5 8 Preliminaryconsiderationsbeforeconnection 5 1 5 9 Preliminary considerations before connection regarding the batteriesandtheirp...

Page 3: ...ingmode Descriptionofstate 7 2 4 3 Warningoralertcodes 7 2 4 4 Errororfaultcodes 7 2 4 5 Warningoralertindicators 7 3 CONTROLPANELFOR4KVATO10KVAMODELS 7 3 1 Audiblealarms 7 3 2 Opticalindications 7 3...

Page 4: ...hough no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images included in thi...

Page 5: ...s of installation and commissioning to be performed in a simple and orderly manner without having any doubts whatsoever Finally once the equipment is installed and operating it is recommended to save...

Page 6: ...may cause radio interference in which case the user must take additional measures SLC TWIN RT2 4 10 kVA This is a category C3 UPS This is a product for commercial and industrial application in the se...

Page 7: ...belling on the equipment itself will always prevail The nameplate of the device shows all of the values relating to its main properties and characteristics Act accordingly for its installation 0 7 to...

Page 8: ...mable at disconnection for non critical loads Connector for connection to external battery module Standard and B1 3 kVA models COM port USB RS232 COM port AC power IEC connector Smart slot protective...

Page 9: ...nnector VDC protection Battery module connector Fig 3 Rear view of battery modules for extended backups PDU for 4 to 6 kVA devices Output circuit breaker Output IEC connectors Output circuit breaker O...

Page 10: ...hout batteries but with a space reserved for installation in the same box for models whose standard version specifies this For other models the battery pack will be installed in the manner considered...

Page 11: ...f the blockage or fault remains contact T S S With the inverter shut down the output supplies mains power directly through the static bypass of the device provided that it has AC input power Frequency...

Page 12: ...interruptions to the power supply of the protected system while preventing unnecessary hazards for the technical personnel 4 5 3 Communication card The UPS features a slot at the rear for inserting o...

Page 13: ...ry module for 0 7 to 3 kVA UPS 1 battery module Information for warranty registration 2 metal pieces for use as handles and screws for installing the unit in a rack cabinet 2 plastic pieces to extend...

Page 14: ...ance is considerable it is recommended to transport the device in its packaging to the installation site and then unpack it 5 1 5 Siting immobilising and considerations All TWIN RT2 series UPSs are de...

Page 15: ...stallation by the user Mount the guides at the required height ensuring correct tightening of the fixing screws and appropriate fitting in the machining according to each case Place the device onto th...

Page 16: ...pper or lower part of the cabinet it is recommended that two people carry out the installation operations Fix the UPS and the battery module to the cabinet frame by means of the screws supplied with t...

Page 17: ...exception The cross section of the cables must always be considered in relation to the size of the terminals of the switches so that they are correctly fastened across their entire cross section for...

Page 18: ...ting systems in parallel only in models 3 kVA To access the signal block it is necessary to remove its protective cover Slot for the integration of one of the optional electronic communication units R...

Page 19: ...C connectors indicated in Fig 2 as critical loads will be reserved Take into account that they are set by default as critical loads The 3 kVA models also have a 16A IEC connector that enables the conn...

Page 20: ...tage to the input terminals Make sure that all of the loads connected to the UPS are only connected to its earth connection terminal Failure to limit the earthing of the load or loads and battery modu...

Page 21: ...erent earths of the control of each UPS In the event of acquiring a manual bypass board through another conduit check that it has this auxiliary contact and connect it to the terminal block of the UPS...

Page 22: ...difference in length between the input and output cables of the device must be less than 20 When the distance between the UPSs in parallel and the circuit breaker board is more than 20 metres the diff...

Page 23: ...View of ViewPower s main screen Installation procedure Go to the web page http support salicru com Select the required operating system and follow the instructions described on the web page to downlo...

Page 24: ...output protections to On Turn the battery switch to On models B0 and B1 Turn the device s input circuit breaker to On Press the ON button for more than 2 seconds the audible alarm will sound for 1 se...

Page 25: ...e manual bypass Otherwise it will be necessary to adapt the board or acquire a new one if it has not been previously anticipated Since it is necessary to change the parallel bus connection to incorpor...

Page 26: ...accidents To prevent incorrect operations it is necessary to fit the mechanical lock and the covers of the manual bypass mechanisms and their fixing screws Press the ON button on all of the UPSs for...

Page 27: ...cates the charge level connected to the output as a by displaying four equivalent segments respectively in the following proportion 0 25 26 50 51 75 and 76 100 Information about programmable outputs P...

Page 28: ...ESC Escape HLS HLS Upper voltage limit for transfer to battery mode LLS LLS Lower voltage limit for transfer to battery mode AO AO EPO normally open AC AC EPO normally closed EAT EAt Estimated backup...

Page 29: ...de it will move downwards through the menu structure in relation to the point where it is located accessing the following variable with each press OFF ENTER UPS shutdown Press this button for at least...

Page 30: ...related to the capacity of the battery pack The charger will adapt the charging factor automatically according to the value of the total capacity entered up to the maximum of the current that is poss...

Page 31: ...tput frequency of 50 Hz CF 60 1 CF with output frequency of 60 Hz 1 With parameter 02 ENA the CF 50 or CF 60 variables are displayed instead of BAT 50 or BAT 60 DIS ECO mode disabled ENA ECO mode enab...

Page 32: ...output voltage from the bypass in ECO mode energy saving LCD display CF mode Description When the input frequency is between 46 and 64 Hz the UPS can be set to a constant output frequency of 50 or 60...

Page 33: ...oo high 28 Battery voltage too low 2A Battery charger short circuited at its output 41 Overtemperature 43 Output overload 45 Charger fault 49 Input overcurrent Tab 13 Error or fault code 7 2 4 5 Warni...

Page 34: ...u structure to the previous variable in relation to the point where it is located ON Starting up the UPS Press the button for at least 2 seconds Confirmation of selection Press this button to confirm...

Page 35: ...options Tab 18 Parameter 1 codes list Description and settings Code 01 Output voltage Fig 27 Parameter 3 setting Output voltage It is possible to choose one of the following values for the output volt...

Page 36: ...ss enabled When selected bypass mode is enabled DIS Bypass disabled If selected automatic bypass is permitted but not manual switch to bypass At this point manual switch to bypass is understood as bei...

Page 37: ...000 TWIN RT2 device with an external battery pack of 45 Ah belonging to it 45 Ah 7 Ah 6 4 When rounding down value 6 must be entered in parameter 3 The basic reason for adjusting the setting is as fol...

Page 38: ...e regulation ranges and ECO mode is activated the UPS supplies the output voltage from the bypass in ECO mode energy saving LCD display ECO CF mode Description When the output frequency is selected as...

Page 39: ...30 minutes 3A Maintenance switch cover open 3D Bypass not available 3E Start up fault Tab 20 Warning or alert code 7 3 4 4 Error or fault codes Code Error or fault description 01 DC bus start up faul...

Page 40: ...which is in turn connected to earth any metal part of the device Repair and or maintenance work must be carried out by our T S S except for the replacement of batteries which can be performed by quali...

Page 41: ...ds from the output sockets After repeated overloads the UPS is locked in Bypass mode The connected loads are powered directly from the mains Disconnect the excess loads from the output sockets shut do...

Page 42: ...he following fault codes 01 02 03 04 11 12 13 14 1A 21 24 35 36 41 42 or 43 are displayed on the LCD display and the audible alarm sounds continuously An internal fault has occurred in the UPS This is...

Page 43: ...0 91 93 Performance at full load in ECO mode 95 96 97 99 Overload in line mode 110 130 5 min 100 110 2 min 130 140 30 sec 110 130 1 min 140 150 1 5 sec 130 1 sec 150 100 ms Overload in battery mode 11...

Page 44: ...ill be 78 of the rated 6 As a frequency converter the power supplied will be 60 of the rated DSP Digital signal processor A DSP is a processor or microprocessor based system that has a set of instruct...

Page 45: ...ing through the visible light spectrum to infrared the latter called IRED infra red emitting diode Circuit breaker A circuit breaker is a device capable of interrupting the electrical current of a cir...

Page 46: ...46 SALICRU...

Page 47: ...47 USER MANUAL...

Page 48: ......

Reviews: