background image

14

are exposed, must be respected, otherwise the warranty 

may be invalidated.

 

After this period, connect the device to the mains together 

with the battery unit if applicable, start it according to the 

instructions described in this manual and charge for 12 

hours.

In parallel systems, it is not necessary to interconnect 

devices before battery charging. Each of them can be 

treated independently to charge them.

 

Then shut down the device, disconnect it and store the UPS 

and batteries in their original packaging, noting the new 

date for recharging the batteries on a document as a record 

or even on the packaging itself.

 

Do not store the devices where the ambient temperature 

exceeds 50ºC or drops below -15ºC, as this may cause 

degradation of the electrical characteristics of the batteries.

5.1.3.  Unpacking. 

 

The packaging of the device consists of a cardboard box, 

expanded polystyrene (EPS) or polyethylene foam (EPE) 

corners, polyethylene cover and strapping, all of which are 

recyclable materials; consequently, if it requires disposal, 

it must be carried out in accordance with current laws. We 

recommend keeping the packaging in case it needs to be 

used in the future.

 

Proceed as follows:

 

ˆ

Cut the straps around the cardboard box.

 

ˆ

Remove the accessories (cables, brackets, etc. )

 

ˆ

Remove the device or battery module from the box with 

the help, if necessary, of a second person depending 

on the weight of the model or using appropriate 

mechanical means.

 

ˆ

Remove the protective corners from the device and the 

plastic bag.

Do not leave the plastic bag within the reach of 

children to avoid danger of suffocation.

 

ˆ

Inspect the device before proceeding and, in the event 

of finding damage, contact the supplier or, failing that, 

our firm.

5.1.4.  Transport to the site.

It is recommended to transport the UPS by means of a 

pallet jack or the most appropriate method considering the 

distance between the two points.

If the distance is considerable, it is recommended to 

transport the device in its packaging to the installation site 

and then unpack it.

5.1.5.  Siting, immobilising and considerations.

 

All TWIN RT2 series UPSs are designed to be mounted as 

a tower model -vertical arrangement of the device- or rack 

-horizontal arrangement- for installation in 19” cabinets, 

regardless of whether they operate independently or as 

parallel systems, whether or not they have a battery module 

or whether the available backup is standard or extended 

(greater number of battery modules).

Follow the instructions indicated in the sections relating to 

either of the two possibilities, according to the particular 

configuration of your device.

 

Figs. 5 to 11 show, by way of example, illustrations of a 

device with or without battery module. These illustrations 

provide help and guidance in the steps to follow, but the 

instructions are not intended to refer to a single model, 

although, in practice, the actions to be carried out are 

always the same for all of them.

 

For all instructions regarding connections, refer to section 5.2.

5.1.5.1.  Rotation of the control panel with LCD display.

Fig. 5. 

Rotation of the control panel with LCD display on 

the plastic front trim.

 

To facilitate the reading of messages on the display when 

the device is installed vertically, it is possible to rotate the 

control panel clockwise by 90º (see Fig. 5).

 

Likewise, reverse the rotation of the control panel if a 

device arranged as a tower needs to be installed as a rack.

In this case, the rotation of the control panel will be anti-

clockwise.

 

Proceed as follows:

 

ˆ

Insert fingertips into the recesses of the plastic trim 

around the display and pull outwards.

 

ˆ

Rotate the control panel with LCD display 90º to the 

right with respect to its initial position and insert it back 

into the front.

5.1.5.2.  Vertical tower-type mounting.

 

Rotate the control panel according to section 5.1.5.1.

 

Take the 4 pieces of plastic supplied with the device and 

join them together in twos to obtain two bases.

 

Place the UPS upright between the two bases at a distance 

of 70 mm from each end (see Fig. 6).

 

 

 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 

Summary of Contents for SLC TWIN RT2 LION

Page 1: ...SLC TWIN RT2 0 7 10 kVA UNINTERRUPTIBLE POWER SUPPLY SYSTEMS UPS USER MANUAL Industriestrasse 17 Tel 061 926 90 60 www sicotec ch CH 4415 Lausen Fax 061 926 90 66 usv sicotec ch SICOTEC AG...

Page 2: ...ower typemountingwithPDU 5 1 5 7 Rackmountingin19 cabinetwithPDU 5 1 5 8 Preliminaryconsiderationsbeforeconnection 5 1 5 9 Preliminary considerations before connection regarding the batteriesandtheirp...

Page 3: ...ingmode Descriptionofstate 7 2 4 3 Warningoralertcodes 7 2 4 4 Errororfaultcodes 7 2 4 5 Warningoralertindicators 7 3 CONTROLPANELFOR4KVATO10KVAMODELS 7 3 1 Audiblealarms 7 3 2 Opticalindications 7 3...

Page 4: ...hough no effort has been spared to ensure that the information in this user manual is complete and accurate we are not responsible for any errors or omissions that may exist The images included in thi...

Page 5: ...s of installation and commissioning to be performed in a simple and orderly manner without having any doubts whatsoever Finally once the equipment is installed and operating it is recommended to save...

Page 6: ...may cause radio interference in which case the user must take additional measures SLC TWIN RT2 4 10 kVA This is a category C3 UPS This is a product for commercial and industrial application in the se...

Page 7: ...belling on the equipment itself will always prevail The nameplate of the device shows all of the values relating to its main properties and characteristics Act accordingly for its installation 0 7 to...

Page 8: ...mable at disconnection for non critical loads Connector for connection to external battery module Standard and B1 3 kVA models COM port USB RS232 COM port AC power IEC connector Smart slot protective...

Page 9: ...nnector VDC protection Battery module connector Fig 3 Rear view of battery modules for extended backups PDU for 4 to 6 kVA devices Output circuit breaker Output IEC connectors Output circuit breaker O...

Page 10: ...hout batteries but with a space reserved for installation in the same box for models whose standard version specifies this For other models the battery pack will be installed in the manner considered...

Page 11: ...f the blockage or fault remains contact T S S With the inverter shut down the output supplies mains power directly through the static bypass of the device provided that it has AC input power Frequency...

Page 12: ...interruptions to the power supply of the protected system while preventing unnecessary hazards for the technical personnel 4 5 3 Communication card The UPS features a slot at the rear for inserting o...

Page 13: ...ry module for 0 7 to 3 kVA UPS 1 battery module Information for warranty registration 2 metal pieces for use as handles and screws for installing the unit in a rack cabinet 2 plastic pieces to extend...

Page 14: ...ance is considerable it is recommended to transport the device in its packaging to the installation site and then unpack it 5 1 5 Siting immobilising and considerations All TWIN RT2 series UPSs are de...

Page 15: ...stallation by the user Mount the guides at the required height ensuring correct tightening of the fixing screws and appropriate fitting in the machining according to each case Place the device onto th...

Page 16: ...pper or lower part of the cabinet it is recommended that two people carry out the installation operations Fix the UPS and the battery module to the cabinet frame by means of the screws supplied with t...

Page 17: ...exception The cross section of the cables must always be considered in relation to the size of the terminals of the switches so that they are correctly fastened across their entire cross section for...

Page 18: ...ting systems in parallel only in models 3 kVA To access the signal block it is necessary to remove its protective cover Slot for the integration of one of the optional electronic communication units R...

Page 19: ...C connectors indicated in Fig 2 as critical loads will be reserved Take into account that they are set by default as critical loads The 3 kVA models also have a 16A IEC connector that enables the conn...

Page 20: ...tage to the input terminals Make sure that all of the loads connected to the UPS are only connected to its earth connection terminal Failure to limit the earthing of the load or loads and battery modu...

Page 21: ...erent earths of the control of each UPS In the event of acquiring a manual bypass board through another conduit check that it has this auxiliary contact and connect it to the terminal block of the UPS...

Page 22: ...difference in length between the input and output cables of the device must be less than 20 When the distance between the UPSs in parallel and the circuit breaker board is more than 20 metres the diff...

Page 23: ...View of ViewPower s main screen Installation procedure Go to the web page http support salicru com Select the required operating system and follow the instructions described on the web page to downlo...

Page 24: ...output protections to On Turn the battery switch to On models B0 and B1 Turn the device s input circuit breaker to On Press the ON button for more than 2 seconds the audible alarm will sound for 1 se...

Page 25: ...e manual bypass Otherwise it will be necessary to adapt the board or acquire a new one if it has not been previously anticipated Since it is necessary to change the parallel bus connection to incorpor...

Page 26: ...accidents To prevent incorrect operations it is necessary to fit the mechanical lock and the covers of the manual bypass mechanisms and their fixing screws Press the ON button on all of the UPSs for...

Page 27: ...cates the charge level connected to the output as a by displaying four equivalent segments respectively in the following proportion 0 25 26 50 51 75 and 76 100 Information about programmable outputs P...

Page 28: ...ESC Escape HLS HLS Upper voltage limit for transfer to battery mode LLS LLS Lower voltage limit for transfer to battery mode AO AO EPO normally open AC AC EPO normally closed EAT EAt Estimated backup...

Page 29: ...de it will move downwards through the menu structure in relation to the point where it is located accessing the following variable with each press OFF ENTER UPS shutdown Press this button for at least...

Page 30: ...related to the capacity of the battery pack The charger will adapt the charging factor automatically according to the value of the total capacity entered up to the maximum of the current that is poss...

Page 31: ...tput frequency of 50 Hz CF 60 1 CF with output frequency of 60 Hz 1 With parameter 02 ENA the CF 50 or CF 60 variables are displayed instead of BAT 50 or BAT 60 DIS ECO mode disabled ENA ECO mode enab...

Page 32: ...output voltage from the bypass in ECO mode energy saving LCD display CF mode Description When the input frequency is between 46 and 64 Hz the UPS can be set to a constant output frequency of 50 or 60...

Page 33: ...oo high 28 Battery voltage too low 2A Battery charger short circuited at its output 41 Overtemperature 43 Output overload 45 Charger fault 49 Input overcurrent Tab 13 Error or fault code 7 2 4 5 Warni...

Page 34: ...u structure to the previous variable in relation to the point where it is located ON Starting up the UPS Press the button for at least 2 seconds Confirmation of selection Press this button to confirm...

Page 35: ...options Tab 18 Parameter 1 codes list Description and settings Code 01 Output voltage Fig 27 Parameter 3 setting Output voltage It is possible to choose one of the following values for the output volt...

Page 36: ...ss enabled When selected bypass mode is enabled DIS Bypass disabled If selected automatic bypass is permitted but not manual switch to bypass At this point manual switch to bypass is understood as bei...

Page 37: ...000 TWIN RT2 device with an external battery pack of 45 Ah belonging to it 45 Ah 7 Ah 6 4 When rounding down value 6 must be entered in parameter 3 The basic reason for adjusting the setting is as fol...

Page 38: ...e regulation ranges and ECO mode is activated the UPS supplies the output voltage from the bypass in ECO mode energy saving LCD display ECO CF mode Description When the output frequency is selected as...

Page 39: ...30 minutes 3A Maintenance switch cover open 3D Bypass not available 3E Start up fault Tab 20 Warning or alert code 7 3 4 4 Error or fault codes Code Error or fault description 01 DC bus start up faul...

Page 40: ...which is in turn connected to earth any metal part of the device Repair and or maintenance work must be carried out by our T S S except for the replacement of batteries which can be performed by quali...

Page 41: ...ds from the output sockets After repeated overloads the UPS is locked in Bypass mode The connected loads are powered directly from the mains Disconnect the excess loads from the output sockets shut do...

Page 42: ...he following fault codes 01 02 03 04 11 12 13 14 1A 21 24 35 36 41 42 or 43 are displayed on the LCD display and the audible alarm sounds continuously An internal fault has occurred in the UPS This is...

Page 43: ...0 91 93 Performance at full load in ECO mode 95 96 97 99 Overload in line mode 110 130 5 min 100 110 2 min 130 140 30 sec 110 130 1 min 140 150 1 5 sec 130 1 sec 150 100 ms Overload in battery mode 11...

Page 44: ...ill be 78 of the rated 6 As a frequency converter the power supplied will be 60 of the rated DSP Digital signal processor A DSP is a processor or microprocessor based system that has a set of instruct...

Page 45: ...ing through the visible light spectrum to infrared the latter called IRED infra red emitting diode Circuit breaker A circuit breaker is a device capable of interrupting the electrical current of a cir...

Page 46: ...46 SALICRU...

Page 47: ...47 USER MANUAL...

Page 48: ......

Reviews: